Toshiba HWT-601XWHM3W-ETR Service Manual page 89

Air to water heat pump
Table of Contents

Advertisement

Item
7-4.
4) Outdoor fan control
Outdoor unit
The outdoor side control part controls the number of fan motor rotations by receiving an operation instruction from the
control
Hydro side (Hydro unit) control part.
For sensing the true outside temperature, fan is operated without compressor operation.
* Although the fan motor is a DC motor, which has non-step variable numbers of rotations, it is limited to some steps for convenience of
control.
The number of fan tap rotation allocation [rpm]
401, 601
801, 1101
401, 601
801, 1101
4-1) Cooling fan control
• The TL sensor, TO sensor and operation frequency control the outdoor fan. The control is performed by 1 tap of
the DC fan control (14 taps).
• For 60 seconds after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After
that, the fan is controlled according to the TL sensor (401, 601), TG (801, 1101). (TG: temperature converted from
PD)
401, 601
TL [ °C]
56
53
38
35
Temperature range
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
801, 1101
TG [°C]
58
55
38
35
Temperature range
29°C ≤ TO < 38°C
15°C ≤ TO < 29°C
5°C ≤ TO < 15°C
Operation flow and applicable data, etc.
W1
W2
240
320
200
200
W9
WA
560
570
410
450
WF tap
+ 1 tap / 20 secs
(Up to the maximum number of rotation for each zone)
Number of rotation hold
- 1 tap / 20 secs
(Up to the minimum number of rotation for each zone)
Less than 20 Hz
Minimum
Maximum
38°C ≤ TO
W6
W5
W4
W3
WF tap
+ 1 tap / 20 secs
(Up to the maximum number of rotation for each zone)
Number of rotation hold
- 1 tap / 20 secs
(Up to the minimum number of rotation for each zone)
Less than 20 Hz
Minimum
Maximum
38°C ≤ TO
W6
W5
W4
W3
W3
W4
W5
W6
320
390
400
470
200
230
260
290
WB
WC
WD
WE
570
650
700
750
480
500
540
570
20 Hz or more to less
than 45 Hz
Minimum
Maximum
WC
W8
WF
WB
W7
WD
W8
W6
WA
W6
W5
W8
20 Hz or more to less
than 45 Hz
Minimum
Maximum
WC
W8
WE
WB
W7
WD
W8
W6
WA
W6
W5
W8
88
W7
W8
510
550
330
360
WF
830
600
45 Hz or more
Minimum
Maximum
WA
WF
W9
WD
W8
WC
W7
WA
45 Hz or more
Minimum
Maximum
WA
WE
W9
WD
W8
WC
W7
WA