Toshiba HWT-601XWHM3W-ETR Service Manual page 73

Air to water heat pump
Table of Contents

Advertisement

Item
7-3.
Example of pump speed control (heating and hot water supply mode including defrost operation)
Hydro Unit Control
Ambient temperature
When the target flow rate is changed, pump speed changes slowly in actual working, it is because of considering for
noise by pump speed changing quickly.
3-2) Controlling the built-in circulation pump P1 during the hot water supply operation
You can change the action of the built-in circulation pump P1 during the hot water supply operation using DN_5A.
• DN_5A = "0" (Default): The pump stops as the HP for hot water supply stops.
• DN_5A = "1": The pump is always energized.
3-3) Controlling the built-in circulation pump P1 during the heating operation
You can change the action of the built-in circulation pump P1 during the heating operation using DN_6D0.
• DN_6D0 = "0" (Default): The pump is always energized.
• DN_6D0 = "1": The pump stops when To ≥ 20°C. (Practically the HP for heating is turned off.)
3-4) Synchronized external circulation pump P2
Pump type: DC motor, rated voltage 220-240 V, connectable directly up to 200W rated power output.
You can select whether the pump P2 is synchronized with the pump P1 using DN_6B5. The pump P2 is always
energized if the pump P2 is not synchronized.
• DN_6B5 = "0" (Default): Non-synchronous
NOTE:
2 zone temperature control by boiler with P1 OFF is required DN_6B5 OFF
3-5) Controlling the external circulation pump P2
You can change the action of the external circulation pump P2 during cooling operation by setting DN_64.
• DN_64 = "00" (Default): The pump is always energized.
• DN_64 = "01": The pump is always stopped.
Operation flow and applicable data, etc.
Item
Heating target considered TO X°C
Target flow rate
Heating target considered TO Y°C
Hot water supply target
Defrost
Heating
Comp. OFF / Thermostat OFF
Hot water supply
Comp. OFF / Heater operation
Status
FL_max
FL_min
0 L/min
ON
OFF
Compressor ON
Operation STOP
Compressor ON
Operation STOP
TO: X°C
TO: Y°C
72