...4 CONFIGURATION
...4.11 Set Up Alarms Page
SEtUP
ALArMS
ALArM
–
tYPE
––––
From page 41
40
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Page Header – Set Up Alarms.
Alarm Identities
Up to ten alarms (A to K but not I) can be programmed.
Each alarm can be assigned an Alarm Type, a Trip Level
and a Hysteresis setting. Alarm A is the highest priority
and K the lowest.
The alarm status l.e.d. indicators are:
Note.
A1
–
alarms A to E
A2
–
alarms F to K.
Select the Alarm identity.
Alarm Type
An alarm type can be assigned to the alarm identity selected
above – Refer to Figs. 4.9 to 4.13.
Select the alarm type:
–
no alarm function
NONE
–
high process
HPrC
–
low process
LPrC
–
high deviation
HdEV
–
low deviation
LdEV
–
high output
HOUt
–
low output
LOUt
–
fast rate
FrtE
(rate of change of process variable)
–
slow rate
SrtE
(rate of change of process variable)
–
mode alarm
MOdE
PEVt
–
program event
SEVt
–
segment event
(a)
Continued on next page.
(b)
From
More Alarms to be Programmed
frame.