ABB C310 Programming Manual page 20

Universal process controllers
Hide thumbs Also See for C310:
Table of Contents

Advertisement

...4.5.1 Set Up Process Variable Input Page
(a)
LIN–HI
LIN–LO
THC / RTD
Type
Type B*
Type E
Type J
Type K
Type L
Type N
Type R & S*
Type T
RTD
* Accuracy for type B,R and S is not guaranteed below 400°C.
Minimum span below zero Type T 70°C/126°F
THC standard DIN 43710 IEC 584
RTD standard DIN 43760 IEC 751
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Linearizer Full Scale
Set the range maximum temperature in °C or °F as
I000
selected at
in Table 4.1
(linearizer overrange) is displayed in the
see Table 5.1a of the Operating Guide .
0
Linearizer Zero
Set the range minimum temperature in °C or °F as selected
at
4.1
(c)
Continued on next page. (for b and c)
Degrees Celsius
Min.
Max.
– 18
1800
– 100
900
– 100
900
– 100
1300
– 100
900
– 200
1300
– 18
1700
– 250
300
– 200
600
Table 4.1 Temperature Limits
Linearizer Units
. If these limits are exceeded,
above,
Linearizer Units
.
Min. Span
Min.
710
45
– 148
50
– 148
65
– 148
50
– 148
90
– 328
320
60
– 418
25
– 328
4 CONFIGURATION...
above,
within the limits detailed
Operating Page
within the limits detailed in Table
Degrees Fahrenheit
Max.
0
3272
1652
1652
2372
1652
2372
0
3092
572
1112
LIN–Or
Min. Span
1278
81
90
117
90
162
576
108
45
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

C300

Table of Contents