ABB C310 Programming Manual page 8

Universal process controllers
Hide thumbs Also See for C310:
Table of Contents

Advertisement

...4.1 Profile Program Page
PG –ENd
LEU.L
tIME
LEVL
More
segments
to set up
Last segment
rEPEAt
HYSt
SEt
POINtS
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
30
x
0
x
1.0
xx
– – – –
0
0
Program End (finish level)
Set the program end level number for the program chosen
at
, between 1 and 30 (12 for C301, 99 for
Program Select
C302).
Program First Segment Start Level
The number shown in the upper display is the start level
number for the first segment.
Set the required value for the start level.
The units are display units between
Display Full Scale.
Segment Time Period
The time number of the currently selected segment is
shown in the upper display.
Set the required time period, between 0 and 999.9 minutes
in 0.1 minute increments.
Segment Finish/Start Level
The number shown in the upper display is the finish level
number for the currently selected segment and the start
number for the next segment.
Set the required value for the segment finish/start level. The
units are display units between display zero and full scale.
Advance to the next parameter,
more segments are to be set-up or
segment is the last segment.
Program Repeat
Each program can be set to repeat up to 99 times or
continuously.
Set the required repeat count, between 0 and 99, or
for continuous repeats.
InFntE
Program Hysteresis Value (for guaranteed ramp/soak)
A hysteresis value can be set in engineering units. Setting
the value to zero turns the guaranteed ramp/soak facility
off. If the process variable deviates beyond the value set,
the program is suspended but continues automatically
when the process variable returns within the set limits. The
hysteresis value applies above and below set point under
all program conditions.
Set the hysteresis value required, within the display range
limits.
Return to top of
Profile Program Page
or
advance to
Set Points Page.
4 CONFIGURATION...
Display Zero
Segment Time Period
if the current
Repeat
and
, if
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

C300

Table of Contents