Input Range Full Scale
Set the input range maximum in electrical units,
limits detailed in Table 4.2.
– to set an input range full scale of 20mA, enter
Example
200 in the input full scale display and advance to decimal
point display. Set the decimal point one place to give a
value of 20.0.
Decimal Point
Set the decimal point position required for both the range
full scale and range zero values.
Input Range Zero
Set the input range minimum in electrical units,
limits detailed in Table 4.2
Broken Sensor Protection Drive
In the event of a fault being detected on the input, the
process variable is driven in the direction of the mode
selected.
Select the broken sensor drive required:
NONE
UP
dN
Continued on the next page.
Min. Start
– 2000
– 20
– 100
0
Table 4.2 Electrical Limits
.
No drive
Upscale drive
Downscale drive.
Max. Value
2000
20
100
8000
within the
within the
Min. Span
2.5
0.25
0.25
10