Terminal Connection Diagrams - Mitsubishi Electric FR-CC2-H315K Instruction Manual

Table of Contents

Advertisement

2.4

Terminal connection diagrams

 When the sink logic is selected
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase
AC power
supply
Control input signals
(No voltage input allowed) ∗2
External thermal relay input
Contact input common
(Common for external power supply transistor)
24V external power
Common terminal
Connector for manufacturer setting
*1
To use separate power supply for the control circuit, remove each jumper at terminal R1/L11 and terminal S1/L21.
*2
The function of these terminals can be changed using the Input terminal function selection (Pr.178, Pr.187, Pr.189).
*3
The function of these terminals can be changed using the Output terminal function selection (Pr.195).
*4
The function of these terminals can be changed using the Output terminal function selection (Pr.190 to Pr.194).
*5
This connector is for manufacturer setting. Do not use.
*6
Plug-in options cannot be used.
*7
For manufacturer setting. Do not use.
*8
To use the RDA signal of the converter unit, select the normally-closed contact input specification for the input logic of the MRS signal or X10
signal of the inverter.
To use the RDB signal of the converter unit, select the normally-open contact input specification for the input logic of the MRS signal or X10 signal
of the inverter.
(For changing the input logic, refer to the Instruction Manual of the inverter.)
32
2. INSTALLATION AND WIRING
2.4 Terminal connection diagrams
MC
MCCB
R/L1
S/L2
T/L3
R1/L11
Jumper
S1/L21
∗1
Earth
(Ground)
RES
Reset
OH
RDI
Contact input
SD
PC
24VDC power supply
+24
supply input
SD
∗6
Connector 1
DC reactor
Inrush current
P/+
limit circuit
N/-
ON
ON
EMC filter
ON/OFF
OFF
OFF
connecter
Main circuit
Control circuit
RDA
RDB
RSO
IPF
FAN
24V
SE
C1
B1
PU
connector
A1
USB
∗5
mini B
TXD+
connector
TXD-
RXD+
RXD-
GND
(SG)
Terminating
VCC
resistor
88R
∗7
88S
Inverter
P/+
N/-
Open collector output ∗4
Inverter operation enable
(NO contact)
MRS
(X10)
Inverter operation enable
(NC contact)
Inverter reset
RES
Instantaneous
power failure
Cooling fan fault
SD
Open collector output common
Sink/source common
Relay output ∗3
Relay output
(Fault output)
RS-485 terminals
Data transmission
Data reception
GND
5V (Permissible load
current 100mA)
∗8