(The output signals may be used in either the sink or source logic independently of the jumper connector position.)
NOTE
• Make sure that the jumper connector is installed correctly.
• Never change the control logic while power is ON.
 Sink logic and source logic
• In the sink logic, a signal turns ON when a current exits from the corresponding signal input terminal.
Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals.
• In the source logic, a signal turns ON when a current enters into the corresponding signal input terminal.
Terminal PC is common to the contact input signals. Terminal SE is common to the open collector output signals.
Current flow concerning the input/output signal
when sink logic is selected
Sink logic
Current
RES R
RDI
R
SD
Converter unit
Inverter
RES R
RDA
X10
SE
SD
Current flow
Jumper connector
Jumper connector
Jumper connector
Sink
connector
Sink
connector
R
SOURCE
SINK
For sink logic
Current flow concerning the input/output signal
when source logic is selected
Source logic
PC
Current
RES R
RDI
R
Converter unit
Inverter
PC
RDA
X10
SE
RES
Current flow
Source
connector
Source
R
connector
R
2. INSTALLATION AND WIRING
2.7 Control circuit
1
2
3
4
5
6
7
8
9
10