Dynamic power reduction by means of inverter Fronius Datamanager 2.0 Controls, connections and displays on the Fronius Datamanager 2.0 Fronius Datamanager 2.0 during the night or when the available DC voltage is insufficient Starting for the first time Further information on Fronius Datamanager 2.0...
Page 4
Type of AC cable Preparing the aluminium cables for connection AC terminals Cross section of the AC cable Connecting the inverter to the public grid (AC) Maximum fuse rating on alternating current side Connection variants on multi-MPP tracker inverters General Multi MPP Tracker Connecting solar module strings to the inverter Safety...
Safety rules Explanation of DANGER! safety notices Indicates immediate danger. ▶ If not avoided, death or serious injury will result. WARNING! Indicates a potentially hazardous situation. ▶ If not avoided, death or serious injury may result. CAUTION! Indicates a situation where damage or injury could occur. ▶...
Any safety devices that are not fully functional must be repaired by an author- ised specialist before the device is switched on. Never bypass or disable protection devices. For the location of the safety and danger notices on the device, refer to the sec- tion headed "General remarks"...
Data protection The user is responsible for the safekeeping of any changes made to the factory settings. The manufacturer accepts no liability for any deleted personal settings. Copyright Copyright of these operating instructions remains with the manufacturer. The text and illustrations are all technically correct at the time of printing. We reserve the right to make changes.
Utilisation not in accordance with the intended purpose comprises: Any use above and beyond this purpose Making any modifications to the inverter that have not been expressly ap- proved by Fronius the installation of components that are not distributed or expressly ap- proved by Fronius.
Fronius shall not be liable for any damage resulting from such action. No warranty claims will be entertained. Proper use also includes: Carefully reading and obeying all the instructions and all the safety and danger notices in the Operating Instructions and Installation Instructions...
Fronius will not accept any costs associated with production downtimes, installer costs, etc., that may arise as the result of a detected arc and its consequences. Fronius accepts no liability for damage that can occur despite the presence of the integrated Arc Fault Circuit Interrupter/extinguishing system ( e.g. caused by...
Page 18
IMPORTANT! Active PV module electronics (e.g., power optimiser) can impair the function of the Arc Fault Circuit Interrupter. Fronius does not guarantee that the Arc Fault Circuit Interrupter will work correctly in combination with active PV module electronics. Reconnection behaviour After detection of an arc, feeding energy into the grid is interrupted for at least 5 minutes.
Data communication and Fronius Solar Net Fronius Solar Fronius Solar Net was developed to make system add-ons flexible to use in a Net and data in- variety of different applications. Fronius Solar Net is a data network that en- terface ables multiple inverters to be linked up using system add-ons.
Note: Fronius Datamanager 2.0 is only available as an option. Cover for option card compartment Description of The "Fronius Solar Net" LED is on: the "Fronius Sol- the power supply for data communication within the Fronius Solar Net / inter- ar Net" LED face protocol is OK...
Overcurrent (current flow > 3 A, e.g. resulting from a short circuit in the Fronius Solar Net ring) Undervoltage (not a short circuit, voltage in Fronius Solar Net < 6.5 V, e.g. if there are too many DATCOM components on the Fronius Solar Net and not...
With this meter, dynamic power reduction can be performed in two ways: Dynamic power reduction by means of inverter For more information see chapter Dynamic power reduction by means of in- verter on page Dynamic power reduction by means of the Fronius Datamanager 2.0 for more info see: manuals.fronius.com/html/4204260191/ #0_m_0000017472...
S0 meter in the consumption branch If dynamic power reduction is subsequently configured using the Fronius Datamanager 2.0 (Inverter user interface - UC Editor menu - Dynamic power re- duction), dynamic power reduction must be deactivated using the inverter (In-...
Using the IP address 192.168.250.181 for the WLAN access point Switch position B Assigned IP address The Fronius Datamanager 2.0 uses an assigned IP address (factory setting dynamic (DHCP)) The IP address can be set on the Fronius Datamanager 2.0 website.
Page 25
WLAN LED Flashing green: Fronius Datamanager 2.0 is in Service mode (IP switch on the Fronius Datamanager 2.0 plug-in card is in posi- tion A or Service mode has been activated via the inverter display, the WLAN access point is open)
Page 26
(10) Fronius Solar Net Master / Slave switch To switch from master to slave mode within a Fronius Solar Net ring IMPORTANT! In slave mode, all the LEDs on the Fronius Datamanager 2.0 plug-in card are off.
When starting the Fronius Datamanager 2.0 for the first time, the Fronius Datamanager 2.0 plug-in card must be installed in the inverter, there must be a Fronius Datamanager Box 2.0 in the Fronius Solar Net ring. IMPORTANT! In order to establish a connection to Fronius Datamanager 2.0, "Obtain IP address automatically (DCHP)"...
Page 28
The inverter establishes the WLAN access point. The WLAN access point re- mains open for 1 hour. The IP switch on the Fronius Datamanager 2.0 can remain in switch position A due to the activation of the WLAN Access Point.
Fronius Datamanager 2.0 web page is displayed. Where necessary, run the technician wizard and follow the instructions Further informa- Further information on the Fronius Datamanager 2.0 and other start-up op- tion on Fronius tions can be found at: Datamanager 2.0...
Controls and indicators Controls and dis- plays (5) (6) (7) (8) Item Description Display For displaying values, settings and menus Monitoring and status LEDs Initialisation LED (red) lights up During the initialisation phase when starting up the inverter If, when starting up the inverter in the initialisation phase, there is a continuous hardware fault Status LED (orange) lights up If, after the initialisation phase, the inverter is in its automatic...
Display Power for the display comes from the mains voltage. Depending on the setting selected in the Setup menu, the display can be kept on all day. (For night mode, see section Display settings) IMPORTANT! The display of the inverter is not a calibrated measuring device. A slight deviation from the utility meter of the energy company is system-re- lated.
Switching off current supply and restarting the inverter Switching off the Turn off the automatic circuit power supply to breaker. the inverter Turn the DC disconnector to the "OFF" switch position. Switching the inverter on again Turn the DC disconnector to the "ON" switch position. Switch on the automatic circuit breaker.
Installation location and position Explanation of DANGER! safety notices Indicates immediate danger. ▶ If not avoided, death or serious injury will result. WARNING! Indicates a potentially hazardous situation. ▶ If not avoided, death or serious injury may result. CAUTION! Indicates a situation where damage or injury could occur. ▶...
IMPORTANT! Fronius will not accept any costs associated with production downtimes, installer costs, etc., that may arise as the result of a detected arc and its consequences. Fronius accepts no liability for fires that can occur despite the presence of the integrated Arc Fault Circuit Interrupter / interruption system (e.g.
When designing the photovoltaic system, ensure that all components are oper- ated within their permitted operating ranges at all times. Observe all the measures recommended by the solar module manufacturer to ensure that the solar module retains its properties in the long term. Obey the regulations of the power supply company regarding connection meth- ods and energy fed into the grid.
Do not install the inverter in: Places where there is an increased risk of damage from farm animals (horses, cattle, sheep, pigs, etc.) Stables or adjoining areas Storage areas for hay, straw, chaff, animal feed, fertilisers, etc. All inverters are designed to be dust-tight. However, in areas with a heavy build-up of dust, the thermal efficiency may still be impaired by dust forming on the cooling surfaces.
Do not install the inverter horizontally on a vertical wall or pillar. Do not install the inverter on a vertical wall or pillar with its con- nection sockets facing upwards. Do not install the inverter overhanging with the connection sock- ets at the top.
Page 40
The airflow within the inverter is from the right to the top (cold air taken in from the right, hot air dissipated out of the top). The exhaust air can reach a temperature of 70 °C. When installing the inverter in a switch cabinet or similar closed environment, it is necessary to make sure that the hot air that develops will be dissipated by forced-air ventilation.
Attaching the Mounting Bracket Safety WARNING! Danger of residual voltage from capacitors. This may result in an electric shock. ▶ Wait for the capacitors to discharge. The discharge time is indicated on the inverter. CAUTION! Danger due to dirt or water on the terminals and contacts of the inverter's con- nection area.
Installing the When installing the inverter on a mast mounting brack- or support, Fronius recommends the et on a mast or "Pole Clamp" kit from Rittal GmbH (or- beam der no. SZ 2584.000). This kit enables the inverter to be in- stalled on round or rectangular masts with the following diameters: Æ...
Fitting the NOTE! mounting brack- When mounted on metal supports, the inverter must not be exposed to rainwa- et to metal sup- ports ter or splashing water from the rear. Provide suitable rainwater protection or splash water protection. The mounting bracket must be securely screwed to at least four points. Do not warp or IMPORTANT! When fitting the mounting bracket to the wall, ensure that the deform the...
Connecting the inverter to the public grid (AC side) Safety WARNING! Danger due to incorrect operation and incorrectly performed work. This may result in serious injury and damage to property. ▶ Only qualified staff are authorised to commission your inverter and only within the scope of the respective technical regulations.
M32 (Ø 18-25 mm) mounted the AC terminals without ferrules. M32 (Ø 7-15mm) enclosed Fronius Symo Advanced M32 (Ø 18-25 mm) mounted M32 (Ø 7-15 mm) enclosed IMPORTANT! When using ferrules for AC cables with a cross-section of 16 mm², the ferrules must be crimped with a right-angled cross-section.
Connecting the IMPORTANT! inverter to the Form loops with the AC cables when connecting them to the AC terminals. public grid (AC) When securing the AC cables using a metric screw joint, ensure that the loops do not protrude beyond the connection area. Otherwise, under certain circumstances it may no longer be possible to close the inverter.
Maximum fuse rating on altern- ating current side Maximum output overcur- Inverter AC output rent protection Symo Advanced 10.0-3-M 10,000 W C 80 A Symo Advanced 12.5-3-M 12,500 W C 80 A Symo Advanced 15.0-3-M 15,000 W C 80 A Symo Advanced 17.5-3-M...
Page 49
In particular cases, and depending on local factors, however, the type A residual-current circuit breaker may trip at the wrong time. For this reason, Fronius recommends that a residual-current circuit breaker that is suitable for frequency converters should be used.
There are 3 terminals for DC+ per MPP tracker. In total there are six terminals for DC-. In the case of inverters with single MPP trackers like the Fronius Eco, there is 1 DC input (MPP tracker) available. The number of PV modules per string connec- tion should be the same.
Page 51
If your installation requires an AFCI (AFPE) according to IEC63027, do not use a DC Con Kit. The Fronius DC Con Kit 25 (4,251,015) can be used to connect a solar module string with a cross-section of up to 25 mm² to the inverter.
Page 52
If your installation requires an AFCI (AFPE) according to IEC63027, do not use a DC Con Kit. The Fronius DC Con Kit 35 (4,251,029) can be used to connect a PV string with a cross-section of up to 35 mm² to the inverter.
▶ Maintenance and servicing in the power stage set of the inverter must only be carried out by Fronius-trained service technicians. CAUTION! Danger due to incorrectly tightened terminals. This may result in heat damage to the inverter, which may lead to fire.
Exact values for sizing the solar modules can be obtained using suitable cal- culation tools, such as the Fronius Solar.creator (creator.fronius.com). IMPORTANT! Before connecting up the solar modules, check that the voltage for the solar modules specified by the manufacturer corresponds to the actual measured voltage.
When installed between 2501 and 3000 m above sea level: 900 V ▶ When installed between 3001 and 3400 m above sea level: 850 V ▶ the Fronius Symo Advanced must not be installed at an altitude exceeding 3400 m above sea level...
(e.g. if there are 2 DC cables, then break out 2 recesses). strings to the in- verter IMPORTANT! Fronius Eco: check the string fuses used (type and rating) before connecting the solar module strings to the inverter. 2.5 - 10 mm²...
Page 57
IMPORTANT! Observe the torque val- ues marked on the side underneath the terminals. If DC cables are laid over the shaft of the DC main switch or across the con- nection block of the DC main switch, they may be damaged when the invert- er is swung in or they may even prevent the inverter from being swung in.
To cater for this eventuality, a suitable blanking cover (item number 42,0405,2094) is available from Fronius as an option. IMPORTANT! If data communication cables are wired into the inverter, observe the following points:...
IMPORTANT! Observe the ESD guidelines when handling option cards. IMPORTANT! Only one Fronius Datamanager in master mode is permitted per Fronius Solar Net ring. Switch any other Fronius Datamanagers to slave mode or remove them. Seal off the unoccupied option card slot by replacing the cover (item number 42,0405,2094);...
Attaching the inverter to the mounting bracket Attaching the in- WARNING! verter to the mounting brack- Danger from inadequate ground conductor connection. This can result in serious injury and damage to property. ▶ The housing screws provide a suitable ground conductor connection for earthing the housing and must NOT be replaced by any other screws that do not provide a reliable ground conductor connection.
Starting for the first time Starting the in- WARNING! verter for the first time Danger due to incorrect operation and incorrectly performed work. This can result in serious injury and damage to property. ▶ Only qualified personnel are authorised to commission your inverter and only within the scope of the respective technical regulations.
Page 65
* Country setup examples The available country setups may change during a software update. Therefore, the following list may not exactly match the display on the inverter. 50Hz International 50 Hz DE2P Deutschland (> 4,6 kVA) Italia ≤ 11,08 kVA 2019 60Hz International 60 Hz - cosPhi(P) 0,9 Italia >...
Maintenance IMPORTANT! When installed outdoors in a horizontal position: once a year, check that all screw joints are tight! Maintenance and servicing may only be carried out by Fronius-trained service technicians. Cleaning Clean the inverter as required with a damp cloth.
Australian Conduits Tightly sealing Ensure that the conduits are tightly sealed. the conduits Seal conduits NOTE! Condensation within the conduits can damage the inverter or components of the photovoltaic systems. To avoid undesirable air circulation and condensation in the conduits: ▶...
Serial Number Sticker for Customer Use Serial number The serial number of the inverter is sticker for cus- located on the rating plate on the bot- tomer use tom of the inverter. Depending on the installation position of the inverter, the serial number can be difficult to access or read, e.g.
Navigation at the menu level Activating dis- Press any key play backlighting The display backlighting is activated. There is an option under "Display Settings - Backlighting" in the SETUP menu to set the display backlighting so that it is on all the time or off all the time. Automatic deac- If two minutes pass without any button being pressed, the display backlighting tivation of dis-...
Fronius Eco: The total current from both measuring channels is displayed. Both channels are shown separately in SolarWeb. Time date - Time and date on the inverter or in the Fronius Solar Net ring Values displayed Energy fed in (kWh / MWh) under the LOG Energy fed into the grid during the period in question.
Page 75
Maximum grid voltage (V) [phase indicator - neutral or phase - phase] Highest grid voltage measured during the period in question When the Enter key is pressed, the individual grid voltages are listed Maximum solar voltage (V) Highest solar module voltage measured during the period in question When the Enter key is pressed, the voltage values for MPP Tracker 1 and MPP Tracker 2 (MPPT1 / MPPT2) are displayed, if MPP Tracker 2 is activated...
SETUP menu item Initial setting The inverter is pre-configured after commissioning has been completely carried out (e.g. using the Installation Wizard) according to the country setup. The SETUP menu item allows the initial settings of the inverter to be changed easily to bring it in line, as closely as possible, with the preferences and require- ments of the user.
The inverter switches from wherever it is on the menu level back to the "NOW" display mode (exception: "Standby" Setup menu item). The display backlighting goes out unless it has been set to ON in Display Set- ting - Backlighting (see Display Setting - Backlighting). The power currently being fed in is displayed or the currently active state code is displayed.
Page 78
An overview of the values that can be changed is displayed. Use the "Up" and "Down" keys Select "Set time" Press the "Enter" The current time appears. (HH:MM:SS, 24- hour clock), the "tens" digit for the hour will flash. Use the "Up" and "Down" keys to se- lect a value for the first digit of the code Press the "Enter"...
Setting range Status / inverter number / protocol type Status Indicates data communication is taking place via Fronius Solar Net or that a data communications error has occurred Inverter number Sets the number (= address) of the inverter in a system with several inverters...
Fronius Solar Net * The protocol type "Interface" only functions when there is no Datamanager card in the inverter. All Fronius Datamanager cards should be removed from the inverter. Running firmware updates or saving detailed information from the inverter to the...
The final step is for the inverter to update the display. The display remains dark for approx. 1 minute while the monitoring and status LEDs flash. Once the firmware update is complete, the inverter enters its start-up phase be- fore going on to start feeding energy into the grid. Unplug the USB flash drive us- ing the "Safely remove hardware"...
Alarm function: ALL / Per- Switching the floating switch contact for permanent and tem- manent: porary service codes (e.g. brief interruption to energy being fed into the grid, a service code occurs a certain number of times a day - can be adjusted in the "BASIC" menu) As soon as GAF mode is selected, the relay is switched on.
The floating switch contact is automatically switched off: If the inverter is not feeding any power into the grid If the inverter is manually switched to Standby mode If the effective power is set to < 10% of the nominal output of the inverter. To activate the Energy Manager function, select the "E-Manager"...
Page 84
Activate/deactivate automatic changeover between summer and winter time IMPORTANT! Only use the automatic summer/winter time changeover func- tion if the Fronius Solar Net ring does not include any LAN- or WLAN-compat- ible system components (e.g. Fronius Datalogger Web, Fronius Datamanager or Fronius Hybridmanager).
Fronius DATCOM mode is always in effect. The inverter supplies 12 V of DC voltage continuously to power the Fronius Solar Net. The display is always active. IMPORTANT! If Fronius DATCOM night mode is set to ON or AUTO when there are Fronius Solar Net components connected, the inverter's current consumption during the night will increase to around 7 W.
Counter deviation / calibration Calibrating the counter Currency Set the currency Setting range 3 characters, A-Z Feed-in tariff Set the remuneration rate for energy fed into the grid Setting range 2 digits, 3 decimal places Factory setting (depends on country setup) CO2 factor Setting the CO2 factor of the energy fed into the grid To check that the fan is working correctly...
PV Ins.- Insulation resistance of the PV system Ext. Lim. - external Limitation U PV 1 / U PV 2* (U PV 2 is not available on the Fronius Symo 15.0-3 208) Current DC voltage at the DC input terminals, even if the inverter is feeding no...
Page 88
Version - version of country setup Origin activated - indicates that the normal country- specific setup is activated. Alternat. activated - indicates that the alternative coun- try-specific setup is activated (for Fronius Symo Hybrid only) Group - group for updating the inverter software MPP Tracker:...
- derating gradient %/V with which the power is reduced Message - indicates whether the dispatch of an info message via Fronius Solar Net is active Version Displays the version and serial numbers of the PC boards in the inverter (e.g. for...
Switching the key lock on and off General The inverter has a key lock function. When the key lock is active, the Setup menu is not accessible, i.e. the setup data cannot be changed accidentally (or maliciously). The code 12321 has to be entered in order to activate / deactivate the key lock. Switching the Press the "Menu"...
At any time, the logging data stored on the USB flash drive can be imported into the Fronius Solar.access software using the FLD file that was logged at the same time, viewed directly in third-party programs (e.g. Microsoft® Excel) using the CSV file logged at the same time.
USB root directory Fronius inverters (Fronius Galvo, Fronius Symo, Fronius Primo or Fronius Eco) Inverter number - can be set in the Setup menu under DAT- If there are several inverters with the same inverter number, the three files will be saved in the same folder. A digit is added to the file name as a suffix (e.g.: DALO_02.fld)
ON - see the Datamanager 2.0 Operating Instructions, section "Setting and displaying the menu items", "Viewing and adjusting parameters in the DATCOM menu item"). On the Fronius Eco or Fronius Symo 15.0-3 208, the buffer memory also func- tions with just a DC supply. Suitable USB...
FAT12 FAT16 FAT32 Fronius recommends that the USB flash drive employed should only be used for recording logging data or updating the inverter software. The USB flash drives should not contain any other data. USB symbol on the inverter display, e.g. in display mode "NOW":...
Page 95
IMPORTANT! To avoid any loss of data, a USB flash drive may only be Do not disconnect removed if the following conditions USB-Stick are met: while LED is flashing! Only remove a USB flash drive via the 'Safely remove USB / HW' item on the SETUP menu The 'Data transmission' LED has stopped flashing or comes on...
The Basic menu Access the Basic Press the "Menu” button menu The menu level appears. Press the unassigned "Menu / Esc" key 5 times "Access Code" is displayed in the "CODE" menu; the first digit starts flashing. Enter the code 22742: Use the "Plus" and "Minus"...
USB log book Activates or deactivates the function for saving all error messages to a USB flash drive AUTO / OFF / ON ON: All error messages are automatically saved to a connected USB flash drive. Input signal How it works: Ext Sig. / S0-Meter / OFF operating mode Ext Sig.: Triggering method: Warning (warning shown on display) / Ext.
Status diagnostics and troubleshooting Status code dis- The inverter performs a system self-diagnosis that automatically detects many play faults that may occur and shows them on the display. This means you are promptly made aware of malfunctions in the inverter or the photovoltaic system, or of any installation or operating faults.
*) *) If the status code is displayed all the time: Notify a Fronius-trained service en- gineer **) Fault is rectified automatically. If this status code is displayed all the time,...
Page 103
Fan 1 error Fan 2 error *) If the status code is displayed all the time: notify a Fronius-trained service en- gineer **) Fault is rectified automatically. If this status code keeps recurring, contact your system engineer...
Page 104
Status codes – Some of the class 4 status codes necessitate intervention by a Fronius-trained Class 4 service technician. Code Description Behaviour Remedy Unable to communicate with the power stage set The inverter will auto- AC module temperature sensor matically attempt to...
Page 105
Code Description Behaviour Remedy Functional incompatibility (one or The inverter will auto- more PC boards in the inverter are matically attempt to not compatible with each other, e.g. connect again and, if Update inverter firm- after a PC board has been re- possible, will resume ware;...
*) If the status code is displayed all the time: notify a Fronius-trained service technician **) If this status code keeps recurring, contact your system engineer Status codes –...
Page 107
Code Description Behaviour Remedy When power derat- If necessary, purge cooling air Power derating caused by ing occurs, a warning openings and heat sink; too high a temperature message is shown on fault is rectified automatically; the display. Internal DSP malfunction Warning message on the display No communication pos-...
Update inverter firm- not compatible with each other, e.g. ing any energy into the ware; *) after a PC board has been re- grid. placed) *) If the status code is displayed all the time: notify a Fronius-trained service en- gineer...
Page 109
(e.g. at http://www.fronius.com); *) Check USB flash drive and the data contained on it or Write or read error oc- Warning message on the replace USB flash drive...
Page 110
Code Description Behaviour Remedy Initialisation error - error Check USB flash drive; re- Warning message on the in file system on USB flash format on PC for FAT12, display drive FAT16 or FAT32 Error during recording of Remove and then reinsert Warning message on the logging data USB flash drive;...
Warning message on the about the internal pro- display cessor status *) If the status code is displayed all the time: Notify a Fronius-trained service technician Class 10 - 12 1000 - 1299- Provide information on the status of the internal processor pro-...
Technical data Fronius Symo Fronius Symo Advanced 10.0-3-M Advanced Input data 10.0-3-M MPP voltage range 270–800 V DC Max. input voltage 1000 V DC (at 1000 W/m²/ -10 °C in an open circuit) Min. input voltage 200 V DC Max. input current (MPP1 / MPP2) 27.0 / 16.5 A (14 A for...
Page 113
Fronius Symo Advanced 10.0-3-M Nominal frequency 50 / 60 Hz Initial short circuit alternating current / phase I 20 A Total harmonic distortion < 1.75% 27.2 A peak / Current (inrush) 5.18 A rms over 5.4 ms Power factor (cos phi) 0–1 ind./cap.
Fronius Symo Fronius Symo Advanced 12.5-3-M Advanced Input data 12.5-3-M MPP voltage range 320–800 V DC Max. input voltage 1000 V DC (at 1000 W/m²/ -10 °C in an open circuit) Min. input voltage 200 V DC Max. input current (MPP1 / MPP2) 27.0 / 16.5 A (14 A for...
Page 115
Fronius Symo Advanced 12.5-3-M 27.2 A peak / Current (inrush) 5.18 A rms over 5.4 ms Power factor (cos phi) 0–1 ind./cap. Maximum output fault current / duration 64 A / 2.34 ms General data Maximum efficiency 97.8% European efficiency U 95.7 / 97.5 / 96.9%...
Fronius Symo Fronius Symo Advanced 15.0-3-M Advanced Input data 15.0-3-M MPP voltage range 320–800 V DC Max. input voltage 1000 V DC (at 1000 W/m²/ -10 °C in an open circuit) Min. input voltage 200 V DC Max. input current (MPP1 / MPP2) 33.0 / 27.0 A...
Page 117
Fronius Symo Advanced 15.0-3-M 27.2 A peak / Current (inrush) 5.18 A rms over 5.4 ms Power factor (cos phi) 0–1 ind./cap. Maximum output fault current / duration 64 A / 2.34 ms General data Maximum efficiency European efficiency U 96.2 / 97.6 / 97.1%...
Fronius Symo Fronius Symo Advanced 17.5-3-M Advanced Input data 17.5-3-M MPP voltage range 370–800 V DC Max. input voltage 1000 V DC (at 1000 W/m²/ -10 °C in an open circuit) Min. input voltage 200 V DC Max. input current (MPP1 / MPP2) 33.0 / 27.0 A...
Page 119
Fronius Symo Advanced 17.5-3-M 27.2 A peak / Current (inrush) 5.18 A rms over 5.4 ms Power factor (cos phi) 0–1 ind./cap. Maximum output fault current / duration 64 A / 2.34 ms General data Maximum efficiency European efficiency U 96.4 / 97.7 / 97.2%...
Fronius Symo Fronius Symo Advanced 20.0-3-M Advanced Input data 20.0-3-M MPP voltage range 420–800 V DC Max. input voltage 1000 V DC (at 1000 W/m²/ -10 °C in an open circuit) Min. input voltage 200 V DC Max. input current (MPP1 / MPP2) 33.0 / 27.0 A...
Page 121
Fronius Symo Advanced 20.0-3-M 27.2 A peak / Current (inrush) 5.18 A rms over 5.4 ms Power factor (cos phi) 0–1 ind./cap. Maximum output fault current / duration 64 A / 2.34 ms General data Maximum efficiency European efficiency U 96.5 / 97.8 / 97.3%...
2 + 2P Rated breaking capa- ≤ 500 city 1000 Integrated DC Settings disconnector Product name Benedict LS32 E 7858 Fronius Symo Advanced 15.0 - Rated insulation 1000 V 20.0 voltage Rated impulse with- 8 kV stand voltage Suitability for insula-...
Page 124
Applicable CE mark standards and The devices comply with all the requisite and relevant standards and guidelines guidelines that form part of the relevant EU Directive, and are therefore permitted to dis- play the CE mark. Circuit to prevent stand alone operation The inverter has an approved circuit to prevent stand alone operation.
Detailed, country-specific warranty terms are available on the internet: facturer's war- www.fronius.com/solar/warranty ranty To obtain the full warranty period for your newly installed Fronius inverter or storage system, please register at: www.solarweb.com. Disposal The manufacturer, Fronius International GmbH, will take back the old device and arrange for it to be recycled in an appropriate manner.
Need help?
Do you have a question about the Symo Advanced 10.0-3-M and is the answer not in the manual?
Questions and answers