Transmitter installation

2.1 
Mounting the transmitter
2.1.1  Mount the transmitter in a liquid application
Procedure
1. Place taps to the side of the line.
2. Mount the transmitter beside or below the taps.
Mount the transmitter so that the drain/vent valves are
oriented upward.
Figure 2-1: Transmitter mounted in an in-line liquid
application
2.1.2  Mount the transmitter in a gas application
Procedure
1. Place taps in the top or side of the line.
2. Mount the transmitter beside or above the taps.
6
July 2023
Rosemount 3051G