Figure 2-8: Wiring
2.4.1  Grounding for transient terminal block
Ground termination is provided on the outside of the electronics
housing and inside the terminal compartment. These grounds are
used when the transient protection terminal blocks are installed.
Emerson recommends using an 18 AWG or larger wire to connect
housing ground to earth ground (internal or external).
If the transmitter is currently not wired for power up and
communication, see
transmitter is properly wired, see
transient grounding locations.
2.5 
Verifying configuration
2.5.1  Verify configuration using any HART
tool or local operator interface (LOI) - option code M4
See
Verifying configuration using a Field Communicator
configuration using a Field Communicator or
with Local Operator Interface (LOI)
LOI.
See the
configuration instructions using AMS
12
C
A. Insulate shield and shield drain wire.
B. Insulate exposed shield drain wire.
C. Connect shield back to the power supply ground.
Connect the wiring and power
Rosemount 3051 Pressure Transmitter Manual
A
DP
B
Figure 2-8
-capable configuration
®
to verify configuration using the
Device Manager.
up. When the
for internal and external
to verify
Verifying configuration
for
Rosemount 3051G
July 2023