which the diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be followed
in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic
build-up on painted surfaces, and only clean the painted
surfaces with a damp cloth. If paint is ordered through
a special option code, contact the manufacturer for more
information.
4. Appropriate cable, glands and plugs need to be suitable
for a temperature of 5 °C greater than maximum specified
temperature for location where installed.
5. The user must ensure that the maximum rated voltage and
current (36 volts, 24 milliamps, d.c.) are not exceeded. All
connections to other apparatus or associated apparatus shall
have control over this voltage and current equivalent to a
category 'ib' circuit according to EN 50020.
6. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
7. Unused cable entries must be filled with suitable blanking
plugs which maintain the ingress protection of the enclosure
to at least IP66.
8. Cable entries and blanking plugs must be suitable for the
ambient range of the apparatus and capable of withstanding a
7J impact test.
9. The 2088/2090 sensor module must be securely screwed in
place to maintain the ingress protection of the enclosure.
10. Some variants of the equipment have reduced markings on
the nameplate. Refer to the Certificate for full equipment
marking.
I1 ATEX Intrinsic Safety
Certificate:
Standards:
Markings:
24
BAS00ATEX1166X
EN60079-0:2012+A11:2013, EN60079-11:2012
II 1 G Ex ia IIC T4 Ga (-55 °C ≤ T
July 2023
≤ +70 °C)
a
Rosemount 3051G