2.5.2 Verifying configuration using a Field Communicator
Prerequisites
A Rosemount 3051 device driver (DD) must be installed on the Field
Communicator to verify configuration. Fast Key sequences for the
latest DD are shown in
DDs, contact your local Emerson representative.
NOTICE
Emerson recommends installing the latest DD to access the complete
functionality. Visit
DD Library.
Procedure
Verify device configuration using the Fast Key sequences in
•
A check (✓) in the first column indicates the basic configuration
parameters. At minimum, verify these parameters as part of
configuration and startup.
•
A (7) in the first column indicates availability only in HART
Revision 7 mode.
Table 2-1: Device Revision 9 and 10 (HART 7), DD Revision 1 Fast
Key sequence
Function
Alarm and Saturation Levels
✓
Damping
✓
Range Values
✓
Tag
✓
Transfer Function
✓
Units
✓
Burst Mode
Custom Display Configuration
Date
Descriptor
Digital to Analog Trim (4 - 20 mA
Output)
Quick Start Guide
Table
2-1. For Fast Key sequences using legacy
FieldComm Group
for information on updating the
Fast Key sequence
HART 7
2, 2, 2, 5, 7
2, 2, 1, 1, 5
2, 2, 2
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
2, 2, 5, 3
2, 2, 4
2, 2, 7, 1, 4
2, 2, 7, 1, 5
3, 4, 2
Quick Start Guide
Table
2-1.
®
HART 5
2, 2, 2, 5, 7
2, 2, 1, 1, 5
2, 2, 2
2, 2, 7, 1, 1
2, 2, 1, 1, 6
2, 2, 1, 1, 4
2, 2, 5, 3
2, 2, 4
2, 2, 7, 1, 3
2, 2, 7, 1, 4
3, 4, 2