Emerson Rosemount 3051G Quick Start Manual page 16

Pressure transmitter with 4-20ma hart protocol (revision 5 and 7)
Hide thumbs Also See for Rosemount 3051G:

Advertisement

Quick Start Guide
Figure 2-10: LOI Menu
2.5.4  Switch HART revision mode
If the HART configuration tool is not capable of communicating with
HART Revision 7, the Rosemount 3051 will load a generic menu with
limited capability. The following procedures will switch the HART
revision mode from the generic menu:
Procedure
Manual Setup → Device Information  → Identification → Message
a) To change to HART Revision 5, Enter: "HART5" in the Message
field
b) To change to HART Revision 7, Enter: "HART7" in the Message
field
Note
See
Table 2-1
is loaded.
2.6 
Step 5: Trim the transmitter
Devices are calibrated by the factory. Once installed, it is
recommended to perform a zero trim on gage pressure transmitters
to eliminate error due to mounting position or static pressure effects.
A zero trim can be performed using either a Field Communicator or
configuration buttons.
16
to change HART revision when the correct device driver
July 2023
Assign PV
HART Revision
Rosemount 3051G