Emerson Rosemount 3051G Quick Start Manual page 8

Pressure transmitter with 4-20ma hart protocol (revision 5 and 7)
Hide thumbs Also See for Rosemount 3051G:

Advertisement

Quick Start Guide
Figure 2-4: Panel and ppe mounting
Panel mount
 
(1)
1.5 / 16 × 1½ panel bolts are customer supplied.
2.2 
In-line gauge transmitter orientation
The low side pressure port (atmospheric reference) on the in-line
gauge transmitter is located in the neck of the transmitter, behind
the housing. The vent path is 360° around the transmitter between
the housing and sensor.
See
Figure
Keep the vent path free of any obstruction, including but not limited
to paint, dust, and lubrication by mounting the transmitter so that
the process can drain away.
Figure 2-5: In-line gauge low side pressure port
Low side pressure port (atmospheric reference)
A
8
(1)
2-5.
Pipe mount
 
July 2023
A
Rosemount 3051G