Vent Configuration: Vertical Termination for 54 PB ONLY
Use 4x6-5/8" Diameter Coaxial Vent. Connect a 8" to 6-5/8" reducer directly to the
fireplace (sku 98900165).
NOTE: The included thimble assembly is not required and may be discarded.
The termination must fall within the shaded area shown in the chart. Use the indicated
restrictor positions.
Up to four elbows (45° or 90°) may be used. Only one horizontal elbow may be used.
40' (12m) max
35 feet (10.5m)
30 feet (9m)
PB 54 Linear Only
25 feet (7.5m)
Exhaust Restrictor # 8
Diffuser Open
20 feet (6m)
6-5/8" Vent (place reducer on fireplace)
15 feet (4.5m)
Exhaust Restrictor # 5
Diffuser Open
6-5/8" Vent (place reducer on fireplace)
10 feet (3m)
5 feet (1.5m)
PB 54 Linear Only
0 feet
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
© Travis Industries
Installation
(for qualified installers only)
Exhaust Restrictor # 10
Diffuser Open
6-5/8" Vent (place reducer on fireplace)
H2
H1
PB 54 Linear Only
Exhaust Restrictor # 6
Diffuser Open
6-5/8" Vent (place reducer on fireplace)
Exhaust Restrictor # 4
Diffuser Closed (stock)
8" Vent
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
This is considered a
vertical elbow
6/3/19 - 1453
33
40' (12m) max
35 feet (10.5m)
30 feet (9m)
25 feet (7.5m)
20 feet (6m)
15 feet (4.5m)
10 feet (3m)
5 feet (1.5m)
0 feet
PB 42 & 54 MV/GSB2 Install