02250236-267 R02
Installation(continued)
Remote Input and Output Signals
The following input and output signals terminal block is equipped in the starter panel.
# Use shielded wires as input signal wires.
Terminal
No.
Description
Remote Operation
C h a n g e - o v e r
S i g n a l
( f o r
Pressure Control
Mode)
Remote Operation
Command Signal
Remote Operation
C h a n g i n g - o v e r
Signal (for Multi-
D r i v e C o n t r o l
Mode)
# Input Signals
Content
When utilizing customer control run,
connect this to the external terminals
of the customer's controller. When
controlled by a customer's controller,
"b" will be indicated on the digital
display. (Only pressure control mode is
allowed.)
Under remote operation, the operation
of the air compressor is controlled
by the input signal from the remote
switch. Under customer control run,
the operation of the air compressor is
controlled by the input signal from the
control panel of the customer.
Before the remote operation of the air
compressor can be used, the operation
switch must be activated. If the mode
of the air compressor is changed to
remote operation a change-over signal
will occur. A character "r" (Remote
mode) is displayed on the left most
position of the digital display.
When remote control is to be used, the
remote operation change-over signal
must occur before activating the remote
operation command signal.
Subject to EAR, ECCN EAR99 and related export control restrictions.
Output Signals
The input signal is approximately 5VDC, 10mA. Use a switch
or a relay contact with the minimum applicable load of this
value.
The input signal is approximately 5VDC, 10mA. Use a switch
or a relay contact with the minimum applicable load of this
value.
10
How to use
Customer Control Run
Change-over Switch
I n s t a l l t h e c u s t o m e r c o n t r o l r u n
change-over switch near the air
compressor.
Switch ON : Customer controlled
operation is running.
S w i t c h O F F : L o c a l o p e r a t i o n i s
running.
Remote Operation & Stop Switch
Install the remote operation & stop
switch for remote control.
Switch ON : Compressor is running.
S w i t c h O F F : C o m p r e s s o r h a s
stopped.
Remote Operation & Stop Switch
Install the remote operation & stop
switch for remote control.
Switch ON : Compressor is running.
S w i t c h O F F : C o m p r e s s o r h a s
stopped.
Remote Operation Change-over
Switch
Install the remote operation change-
over switch near the air compressor.
Switch ON : Remote operation is
running.
S w i t c h O F F : L o c a l o p e r a t i o n i s
running.