Sullair SRL-7.5MB User Manual page 10

Oil free scroll compressor
Table of Contents

Advertisement

02250236-267 R02
Installation(continued)
【Please see the table below for Reference 】
■ Generated Heat & Required Ventilating Capacity Table
The required ventilating capacity value is the required capacity to keep the temperature rise in the room
within 9°F (5℃ ) when only one Oil Free Scroll Air Compressor is operating.
Item
Generate Heat
Cooling Air Flow
scfm (m
Cooling Air Differential Temperature
Required ventilating capacity (1)
scfm (m
Required ventilating capacity (2)
scfm (m
● Keep the ambient room temperature between 32°F and 104°F (0°C and 40°C). If the temperature
exceeds 104°F (40°C) or there is a defect in the installation, the air compressor protective devices
may stop air compressor operation and/or damage or reduction in compressor life may occur.
● The air compressor discharges air exhaust from the top. Make sure that there are no items such as
lights, or wirings that are above the air compressor that can be affected by the exhaust air.
● Do not modify the intake or exhaust of the air compressor package, otherwise the temperature may
become unbalanced, resulting in the protective devices of the air compressor functioning improperly.
● Do not install ducting on the intake or the exhaust of the Oil Free Scroll Air Compressor, as it may
cause damage to the air compressor.
● Do not operate the air compressor on the pallet of the shipping crate.
● Do not install the air compressor in an area where vibration will negatively effect its surroundings.
5. Install the Air Compressor on Level Ground with a Sufficient
Weight Load. If there is a gap between the air compressor
and the ground, adjust the gap with the attached rubber
vibration isolators to eliminate the gap.
● Do not install the air compressor on ground with
insufficient weight load. Do not operate the air
compressor attached to a pallet or packaging table.
● Do not install on any type of rubber other than the
attached rubber vibration isolators and do not bolt to
concrete. This may result in excessive vibration
and/or damage to the air compressor.
6. For parallel operation, install the air compressors as shown
in the figure to the right. If the air compressors cannot be
installed as shown in the figure to the right, install in a way
that prevents the exhaust of one air compressor from
entering the air intake of the other air compressor.
Subject to EAR, ECCN EAR99 and related export control restrictions.
SRL-7.5MB6LL
Model
SRL-7.5MB6ML
SRL-7.5MB6LH
SRL-7.5MB6MH
kJ/h
25,116
3
/min)
990 (28)
63 (35)
°F (℃ )
2,472 (70)
3
/min)
777 (22)
3
/min)
WARNING
WARNING
SRL-11MB6LL
SRL-16.5MB6LL
SRL-11MB6ML
SRL-16.5MB6ML
SRL-11MB6LH
SRL-16.5MB6LH
SRL-11MB6MH
SRL-16.5MB6MH
36,000
54,000
1,240 (35)
1,520 (43)
63 (35)
63 (35)
3,532 (100)
5,297 (150)
1,130 (32)
1,695 (48)
Intake air
39 in. (991 mm)
or more
6
Rubber vibration
isolators
Install the Air Compressor
on Level Ground with a
Sufficient Weight Load.
Exhaust air
Exhaust air
Intake air