Maintenance - baltur TBML 200 ME Instruction Manual For Installation, Use And Maintenance

Progressive/modulating two-stage mixed gas/diesel burners
Table of Contents

Advertisement

Available languages

Available languages

MAINTENANCE

Analyse combustion gases and check that the emission values are
correct at least once a year, in compliance with current law.
• Clean air damper, the air pressure switch with pressure port and the
relevant pipe, if any.
• Check the electrode condition. Replace them, if necessary.
• Clean the photocell. Replace it, if necessary.
• Have the burner and the chimney cleaned by specialised personnel
(stove repairer); a clean burner is more efficient, lasts longer and is
quieter.
• Check that the fuel filter is clean. Replace it, if necessary.
• Check that all components of the combustion head are in good con-
dition, have not been deformed and are free from deposits deriving
from the installation environment and/or from poor combustion.
• Analyse combustion gases and check emissions values.
If the combustion head needs to be cleaned, remove the components
following the procedure indicated below:
• Disconnect the diesel hoses (24) from the connectors beneath the
head unit (mind the dripping).
• Unscrew the two screws (12) and turn the burner around the pin (31)
in the hinge.
• After pulling the ignition and ionisation cables (14) out of their
electrodes, unscrew the locking nuts (6) from the mixing unit. Lo-
osen nut (9) and completely unscrew the fastening screw on the
delivery coupling (19).
33 / 52
0006160032_202011
ENGLISH

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Tbml 260 meTbml 360 me