D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN
To Walk Test a Door point connected to a
D9210B Access Interface Module, the
door must be opened without activating
the door sequence or allowing it to time
out past the extended shunt time.

L## Fire Test

Default:
See
Program Record Sheet
Selection:
Blank or E
#12 Fire Test [COMMAND][5][8]
Initiate a Fire Walk Test for all 24-hour points in the
area where this command center is assigned.
When a Fire Test is initiated, one person can test a
fire system without assistance. The following features
are provided with the Fire Test Mode:
During this test, the battery powers the control
panel only. A Battery Test is initiated during the
full duration of the test to ensure the battery
capacity is capable of supporting the full load of
the control panel while AC is failed.
-
This test includes a 2-second Bell Test (Fire
Bell relay) for each Fire point that is tested.
-
The test ends once all points are tested or
until the test times out after 20 minutes of
no activity.
Local alarm annunciation and event printing
without reporting to the central station receiver.
Automatic smoke detector reset Sensors
Resetting for all Fire points programmed with
P## Resettable
D1255 command center displays a sequential
count after each point is activated and restored,
as well as the text for the point.
If enabled in Routing, Fire Walk Start and Fire
Walk End are reported at the central station
receiver for the beginning and end of the test.
A# Verify Time for Fire points
programmed with P## Alarm Verify as
Yes is ignored during the Fire Walk Test.

L## Send Report

Program Record Sheet
Default:
See
Selection:
Blank or E
#13 Send Report [COMMAND][4][1] or
[COMMAND][4][2]
Send a Test Report from any command center
assigned to an area where the user has authority.
Bosch Security Systems | 10/03 | 47775E
as Yes.
Access Control Functions
The following functions enable the user to control
the doors using the command center. Users can have
authority to access the Door Control and can use
either all or part of the functions within.
All doors display when this function is
chosen. This function does not follow the
scope of the command center.

L## Door Control

Program Record Sheet
Default:
See
Selection:
Blank or E
#14 Door Control [COMMAND][4][6]
This item only allows programming access to the
following three sub-prompts. It does not affect the
user's access to Cycle Door, Unlock Door, and
Secure Door.
Cycle Door, Unlock Door, and Secure
Door cannot be accessed through the
Function List. Door Control must be added
to the Function List to access the door
control functions, or COMMAND 46 may
be used.
The following prompts are sub-functions of Door
Control. They become visible in the D5200
Programmer when you Enable Door Control and
press [ENTER] on the D5200.
0101
Cycle Door must be enabled for all three
0101
sub-functions to operate. If Cycle Door is
0101
disabled, all three sub-functions do not
operate.

L## Cycle Door

Default:
See
Program Record Sheet
Selection:
Blank or E
Cycle Door (MENU FUNCTION only)
Press the command center number keys [1] through
[8] that correspond to the door number to cycle
doors. For example, pressing [2] and [ENTER]
cycles door number 2, which is indicated by C in the
display.
Cycle Door allows the user with this authority level
to access the CYCLE? 12345678 function.
EN | 61