D9412G/D7412G | Program Entry Guide | 4.0 RADXPNTS

P## Buzz On Fault

Default:
Blank
Selection:
Blank, 1 to 3
Selection
Operation for Controlled Points
(Point Types 1, 2, and 3)
Blank
The point only generates a buzz at the command
center if it goes into the trouble condition
indicated in the P## Point Response.
1
The point generates a Buzz Until Restore at the
command center for any fault condition while the
point is disarmed. The buzz continues until the
point restores and the user acknowledges the
condition using a passcode or COMMAND 4.
The point must be normal before the user can
silence the buzz.
2
The point generates a buzz at the command
center for any fault condition when the point is
disarmed. The point does not need to be normal
before the user can silence the buzz.
3
The point generates a buzz at the command
center for any fault condition when the area is
disarmed. The user cannot silence this buzz, but
it silences automatically when the point is
restored. If the fault condition results in a trouble
response, the command center continues to buzz
even after the user acknowledges the condition if
the fault is still present.
The buzz does not automatically stop once
the point is restored when using Option 1 or
2. The user must acknowledge the buzz
prior to the buzz stopping. However, when
using Option 3, the buzz automatically stops
when the point restores to normal without
user intervention.
Points bypassed (by the user, Sked,
Swinger Bypass, or RAM) do not generate a
Buzz On Fault condition at the command
center.
Bosch Security Systems | 10/03 | 47775E
Operation for 24-hour Points
(Point Type 0)
Same
The point generates a Buzz Until Restore at the
command center for any fault condition regardless
of the armed state. The buzz continues until the
point restores and the user acknowledges the
condition using a passcode or COMMAND 4.
The point must be normal before the user can
silence the buzz.
The point generates a buzz at the command
center for any fault condition regardless of the armed
state. The point does not need to be normal
before the user can silence the buzz.
The point generates a buzz at the command
center for any fault condition regardless of the
armed state. The user cannot silence this buzz,
but it silences automatically when the point is
restored. If the fault condition results in a trouble
response, the command center continues to buzz
even after the user acknowledges the condition if
the fault is still present.

P## Watch Point

Program Record Sheet
Default:
See
Selection:
Yes or No
Yes
This point activates Watch Mode
responses if it is faulted while the
control panel is in Watch Mode.
No
Do not activate Watch Mode responses
for this point.
Use this option to allow a Controlled point to
generate a watch tone as long as the area is disarmed
and not being faulted into a trouble or alarm
condition.
EN | 85