D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS

7.0 RADXAXS

7.1

Door Profile

This programming category is used to:
Assign an area, that also activates the D9210B
Assign a point to the door
Program the door state to change when the arm
state changes
Allow for the Strike relay to activate upon a fire
alarm

Door #

Default:
20 seconds
Selection:
1 seconds to 8 seconds
Enter the number of the door you are about to
program.
The D9412G supports up to eight doors.
The D7412G supports two doors.

D# Entry Area #

Default:
Blank
Selection:
Blank, 1 to 8
1 to 8
The area assigned to the door
controller to which the reader allows
access.
Blank
Door controller does not function.
Assign an area to the door controller. This entry
allows the D9210B to be polled, activating
communication to the control panel. This also is the
area a user exits when initiating a REX.
All SDI devices, regardless of area
assigned, report to Area 1, Account 1 by
default upon SDI failure. If a D9210B
becomes disconnected, an SDI Fail ##
and a Missing Point ### Event is created.
0101
9210 NOT READY appears at this
0101
command center when you press the
0101
[ENTER] key if the D9210B is not
programmed with a D# Entry Area.
Bosch Security Systems | 10/03 | 47775E

D#CC#Scope

Default:
Blank
Selection:
Blank, 1 to 8
1 to 8
Determines disarming rights. The
user's access level in conjunction with
CC # Scope
the
areas are disarmed.
Blank
Only the area assigned to the
Entry Area
Enter the command center number (CC#) which
determines the scope of the user ID's disarming
rights. Areas disarm on the basis of this command
center's scope and the authority level of the user.

D# Door Point

Default:
Blank
Selection:
Blank, 1 to 127, 129 to 247
1 to 127,
The point number assigned to this
129 to 247
door. Points 128 and 248 are reserved
by the control panel for internal use.
Blank
There is no point number assigned to
this door.
Enter the point number assigned to this door. This
point cannot be used for any other point
assignments.
Door points must be programmed as
Perimeter points. If a 24-hour point type is
required for the Door point, you may use a
Perimeter point type with a point response
of 9 to C. Also, the debounce count must
be set to 4 in Point Assignments.
0101
When assigning Points 1 to 8 (control
0101
panel zones), the end-of-line (EOL)
0101
resistors must be removed from the control
panel. In addition to this, do not enable any
POPIT points (or OctoPOPIT points)
sharing the same point number as the
Door point. Failure to do so results in extra
point trouble conditions upon reboot.
EN | 131
determines which
D#
disarms this door.