Watts AERCO Benchmark 2.0 LN Operating & Maintenance Instructions page 69

Benchmark 2.0 gas fired low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0 LN:
Table of Contents

Advertisement

FAULT MESSAGE
RESIDUAL
FLAME
HEAT DEMAND
FAILURE
IGN BOARD
COMM FAULT
DIRECT DRIVE
SIGNAL FAULT
REMOTE SETPT
SIGNAL FAULT
OUTDOOR TEMP
SENSOR FAULT
OUTLET TEMP
SENSOR FAULT
FFWD TEMP
SENSOR FAULT
HIGH WATER
TEMPERATURE
LINE VOLTAGE
OUT OF PHASE
STEPPER MOTOR
FAILURE
NETWORK COMM
FAULT
FAULT MESSAGES - Continued
FAULT DESCRIPTION
The Flame signal was seen for more than 60 seconds during
standby.
The Heat Demand Relays on the Ignition board failed to
activate when commanded.
A communication fault has occurred between the CPU board
and Ignition board.
The direct drive signal is not present or is out of range.
The remote setpoint signal is not present or is out of range.
The temperature measured by the Outdoor Air Sensor is out
of range.
The temperature measured by the Outlet Sensor is out of
range.
The temperature measured by the FFWD Sensor is out of
range.
The temperature measured by the Outlet Sensor exceeded
the Temp Hi Limit setting.
The High AC voltage is out of phase from the low AC voltage.
The stepper motor failed to move the valve to the desired
position.
The RS-485 network information is not present or is
corrupted.
APPENDIX B
B-3