Gas Supply Piping - Watts AERCO Benchmark 2.0 LN Operating & Maintenance Instructions

Benchmark 2.0 gas fired low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0 LN:
Table of Contents

Advertisement

2.3.3 CONDENSATE DRAIN & PIPING
The Benchmark Boiler is designed to condense
water vapor from the flue products. Therefore,
the installation must have provisions for suitable
drainage or collection. A 1/2" NPT drain
connection is provided on the exhaust manifold
(see Fig 2.4). A separate condensate drain trap
(part no. 24060) is shipped loose and must be
installed on the floor behind the unit. Connect
the trap to the exhaust manifold as follows:
1. First, install a 1/2" NPT nipple in the
condensate drain port (Fig. 2.4). Next,
connect a 3/4-to 1/2" reducer to the 1/2"
nipple.
2. On the condensate drain trap, install 3/4"
NPT nipples in the tapped inlet and outlet of
the trap.
3. Attach a length of 1" I.D. polypropylene hose
between the exhaust manifold drain and the
inlet side of the condensate trap (Fig 2.5).
Secure both ends of the hose with clamps.
Drainage from the condensate drain trap
outlet must be by gravity to a nearby floor
drain via a polypropylene hose or suitable
piping.
If a floor drain is not available, a condensate
pump can be used to remove the condensate to
drain. The maximum condensate flow rate is 11
GPH.
The condensate drain trap, associated
fittings and drain line must be removable for
routine maintenance. Do Not hard pipe.
EXHAUST
MANIFOLD
3/4" NPT
CONDENSATE
TRAP
1/2" NPT CONDENSATE
DRAIN CONNECTION
Figure 2.4
Condensate Drain Connection Location
INSTALLATION
EXHAUST
MANIFOLD
CONDENSATE
DRAIN CONNECTION
1" I.D.
CONDENSATE
HOSE
TRAP
CLAMP
TO
FLOOR
DRAIN
1" I.D.
3/4" NPT
HOSE
NIPPLES
Figure 2.5
Condensate Trap Installation

2.4. GAS SUPPLY PIPING

The AERCO Gas Fired Equipment Gas Com-
ponents and Supply Design Guide (GF-2030LN)
must be consulted before any gas piping is
designed or started.
WARNING!
DO NOT USE MATCHES, CANDLES,
FLAMES
OR
OTHER
IGNITION TO CHECK FOR GAS LEAKS
CAUTION!
Many soaps used for gas pipe leak testing
are corrosive to metals. Therefore, AERCO
recommends the use of non-corrosive
soaps for leak tests. The piping must be
rinsed thoroughly with clean water after leak
checks have been completed.
NOTE:
All gas piping must be arranged so that it
does not interfere with removal of any
cover, inhibit service or maintenance, or
prevent access between the Unit and walls,
or another unit.
The location of the 2" inlet gas connection is on
the rear of the unit as shown in Figure 2.5.
All pipes should be de-burred and internally
cleared of any scale or iron chips before
installation. No flexible connectors or non-
approved gas fittings should be installed. Piping
CLAMPS
SOURCES
OF
.
2-3