Watts AERCO Benchmark 2.0 LN Operating & Maintenance Instructions page 60

Benchmark 2.0 gas fired low nox boiler
Hide thumbs Also See for AERCO Benchmark 2.0 LN:
Table of Contents

Advertisement

TROUBLESHOOTING
FAULT INDICATION
PROBABLE CAUSES
continued
3. Control Box signal type
selection switches not set for
correct signal type (voltage or
current).
RESIDUAL
1. SSOV not fully closed.
FLAME
2. Defective Flame Detector.
SSOV FAULT
See SSOV SWITCH OPEN
DURING PURGE
SSOV FAULT
1. SSOV switch closed for 15
seconds during run.
DURING RUN
SSOV RELAY
1. SSOV relay failed on board.
FAILURE
SSOV
1. Actuator not allowing for full
closure of gas valve
SWITCH OPEN
2. SSOV powered when it should
not be
3. Defective Switch or Actuator
4. Incorrectly wired switch.
STEPPER MOTOR
1. Air/Fuel Valve out of calibration.
FAILURE
2. Air/Fuel Valve unplugged.
3. Loose wiring connection to the
stepper motor.
8-9
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
1. Check DIP switch on PMC board to ensure it is set correctly for the type of
signal being sent. Check control signal type set in Configuration Menu.
1. Check open/close indicator window of Safety Shut-Off Valve (SSOV) and
ensure that the SSOV is fully closed. If not fully closed, replace the valve and
or actuator.
Close gas shut-off valve downstream of SSOV. Install a manometer or gauge
in a gas test port between the SSOV and the gas shut off valve. If a gas
pressure reading is observed replace the SSOV valve and or actuator.
2. Replace Flame Detector.
1. Replace or adjust microswitch in SSOV actuator. If fault persists, replace
actuator.
1. Press CLEAR button and restart unit. If fault persists, replace
Ignition/Stepper (IGST) Board.
1. Observe operation of the Safety Shut-Off Valve (SSOV) through indicator on
the Valve actuator and ensure that the valve is fully and not partially closing.
2. If the SSOV never closes, it may be powered continuously. Close the gas
supply and remove power from the unit. Refer fault to qualified service
personnel.
3. Remove the electrical cover from the SSOV and check switch continuity. If
the switch does not show continuity with the gas valve closed, either adjust
or replace the switch or actuator.
4. Ensure that the SSOV Proof of Closure switch is correctly wired.
1. Refer to GF-112 and perform Stepper Test (para. 6.3.5) to ensure stepper
motor rotates properly between the 0% (fully closed) and 100% (fully open)
positions. Verify that the FIRE RATE bargraph and the dial on the Air/Fuel
Valve track each other to indicate proper operation. If operation is not
correct, perform the Stepper Feedback Calibration (GF-112, para. 6.2.1).
2. Check that the Air/Fuel Valve is connected to the Control Box.
3. .Inspect for loose connections between the Air/Fuel Valve motor and the
wiring harness.
CORRECTIVE ACTION

Advertisement

Table of Contents
loading

This manual is also suitable for:

G-05-1393

Table of Contents