APPENDIX A
BOILER MENU ITEM DESCRIPTIONS - Continued
MENU LEVEL & OPTION
Setpt Limiting
Setpt Limit Band
TUNING MENU
Prop Band
Integral Gain
Derivative Time
Reset Defaults?
A-4
DESCRIPTION
Allows Setpoint Limiting to be enabled or disabled.
Default is disabled.
If Setpoint Limiting is enabled, this menu item allows
the Setpt Limit Band to be set from 0°F to 10°F.
Default is 5°F.
Generates a fire rate based on the error that exists
between the setpoint temperature and the actual
outlet temperature. If the actual error is less than
the proportional band setting (1 to 120°F), the fire
rate will be less than 100%. If the error is equal to
or greater than the proportional band setting, the fire
rate will be 100%. Default is 70°F.
This sets the fraction of the output, due to setpoint
error, to add or subtract from the output each minute
to move towards the setpoint. Gain is adjustable
from 0.00 to 2.00. Default is 1.00.
This value (0.0 to 2.00 min.) responds to the rate of
change of the setpoint error. This is the time that
this action advances the output. Default is 0.0 min.
Allows Tuning Menu options to be reset to their
Factory Default values.