Post-Mounting Check - Endress+Hauser Liquiphant FTL33 Operating Instructions Manual

Point level switch for liquids in the food industry
Hide thumbs Also See for Liquiphant FTL33:
Table of Contents

Advertisement

Mounting
View, dimensions in mm (in)
5.3

Post-mounting check

 Is the device undamaged (visual inspection)?
 Does the measuring device meet the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
• Switch point
Are the measuring point identification and labeling correct (visual inspection)?
 Is the device adequately protected from wet conditions and direct sunlight?
18
Description
• DIN11851 DN25 PN40 (milk pipe)
47.9 (1.9)
• DIN11851 DN32 PN40 (milk pipe)
• DIN11851 DN40 PN40 (milk pipe)
Pressure and temperature (maximum):
+25 bar (+362 psi) at +150 °C (+302 °F)
+40 bar (+580 psi) at +100 °C (+212 °F)
A0022036
Tri-Clamp ISO2852 DN25-38 (1 to 1 ½")
47.9 (1.9)
DIN32676 DN25-40
Tri-Clamp ISO2852 DN40-51 (2")
DIN32676 DN50
Pressure and temperature (maximum):
+25 bar (+362 psi) at +150 °C (+302 °F)
NOTICE
A0022035
Flush mount installation in weld-in adapter RD52, tuning fork
47.9 (1.9)
can be aligned
With silicon seal and slotted nut
Pressure and temperature (maximum):
• +25 bar (+362 psi) at +150 °C (+302 °F)
• +40 bar (+580 psi) at +100 °C (+212 °F)
A0022038
Pay attention to the temperature and pressure specifications
for the seals and clips used at the customer site.
Liquiphant FTL33
Endress+Hauser