5.4.2
Level measurement
• Always install the device below the lowest measuring point.
• Do not install the device at the following positions:
– In the filling curtain
– In the tank outlet
– In the suction area of a pump
– Or at a point in the tank which could be affected by pressure pulses from the agitator.
5.5
Mounting the profiled seal for the universal process
adapter
For details on mounting, see KA00096F/00/A3.
5.6

Post-installation check

Is the device undamaged (visual inspection)?
Does the device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature range
• Measuring range
Are the measuring point identification and labeling correct (visual inspection)?
Is the device adequately protected from precipitation and direct sunlight?
Are the securing screws tightened securely?
Installation
A0024405
17