Figure 34. Powerware Hot Sync CAN Bridge Card Connections
Table 21. Powerware Hot Sync CAN Bridge Card Interface Connections
J3 Terminal
1
2
Alarm Return
3
Alarm Relay NC
4
Alarm Relay Com
5
Alarm Relay NO
6
7
8
9
10
J3
Connections for Parallel System Control
Connections for RMP II, RIM II, or SCM II
Connections for Bypass Status
Alarm
Name
Description
Alarm
Programmable UPS alarm. Activated by a remote dry contact closure.
Normally closed contact opens when UPS is on bypass.
Bypass contact return.
Normally open contact closes when UPS is on bypass.
TX
RMP II, RIM II, and SCM II connections.
TX
CAN L
CAN Input for parallel operation.
Can H
Shield
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201710—Rev 14