Eaton Power Xpert 9395 UPS Plus 1 Installation And Operation Manual page 37

Table of Contents

Advertisement

UPS Installation Plan and Unpacking
Table 4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Power Xpert
9395-275/225
Power Xpert
9395-275/275
Figure 2. UPS Cabinet Dimensions (Front View)
16
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201710—Rev 14
Input/Output
Rating
Voltage
400/400
225 kVA
480/480
400/400
275 kVA
480/480
Dimensions are in millimeters [inches].
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
43 (10943)
44 (11054)
Approximately 1652 liter/sec (3500 CFM)
53 (13375)
54 (13510)
Ventilation Required for
Cooling Air Exhaust

Advertisement