Multiple Ups Distributed Bypass System - Eaton Power Xpert 9395 UPS Plus 1 Installation And Operation Manual

Table of Contents

Advertisement

If at any time during the battery discharge the input power becomes available again, the rectifier begins to
supply DC current to the inverter. At this point, the UPS returns to Online mode. If at any time during the
battery discharge the AC input power becomes available again, each rectifier turns on, assumes the inverter
load from the batteries, and begins recharging the batteries. Depending on the total load and the duration of the
battery discharge, battery and rectifier input current limit alarms may be seen for a short time due to the current
required to recharge the batteries.
6 6 . . 5 5
M M u u l l t t i i p p l l e e U U P P S S D D i i s s t t r r i i b b u u t t e e d d B B y y p p a a s s s s S S y y s s t t e e m m O O n n e e l l i i n n e e C C o o n n f f i i g g u u r r a a t t i i o o n n s s
The distributed bypass system oneline drawings in this section show the simplified internal structure of the
UPS, battery supply, and basic maintenance bypass in a multiple UPS configuration. These onelines do not
show each UPM in the UPSs, but represent each UPS in the distributed bypass system. The internal structure
of each UPS is shown in
Oneline Drawing
Figure 58
Figure 59
Figure 60
Figure 51
through
Figure
53.
UPS Model
Input
9395-275/225
400
9395-275/275
480
9395-275/225
400
9395-275/275
480
9395-275/225
400
9395-275/275
480
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201710—Rev 14
Understanding UPS Operation
Voltage
Output
Multiple UPS – Distributed Bypass
400
1+1 and 2+0 Configurations
480
Multiple UPS – Distributed Bypass
400
2+1 and 3+0 Configurations
480
Multiple UPS – Distributed Bypass
400
3+1 and 4+0 Configurations
480
System Type
105