2-8.8
Relay Outputs
The Main Controller Board includes three Form-C, programmable relays and one Form-C, dedicated
Trouble relay. All of these relays have the following contact ratings:
3.0 A @ 24 Vdc (resistive)
3.0 A @ 120 Vac (resistive)
The Relay Expansion Card includes four Form-C, programmable relays as shown in Figure 2-34. All
of these relays have the following contact ratings:
3.0 A @ 24 Vdc (resistive)
3.0 A @ 120 Vac (resistive)
On-board Field-Configurable
Relays (3)
On-board Dedicated
Trouble Relay (1)
February 2011
Relays (located on MCB and Relay Expansion Card)
TB1
TB2
TB3
TB4
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
Figure 2-34. Relay Outputs Diagram
2-42
Field-Configurable
Relays (4)
RELAY 1
RELAY 2
RELAY 3
Installation Note:
1. All relay outputs shown in normal standby condition.
2. All contacts are dry contact type.
RELAY 4
3. Outputs of all relays are not supervised.
4. Ratings - 3 Amps @ 30 Vdc or 3 Amps @ 120 Vac.
5. Maximum of one 12 AWG wire per terminal.
Relay 1
Relay 2
Relay 3
Relay 4
P/N 06-237041-001