Configuration and Programming
Note: All control modules must be manually de-activated via a menu operation or a system reset
before the system can be returned to normal operating condition.
There is no indication at the control unit that an output is activated. Be sure to de-activate
the output after proper operation has been confirmed.
Ensure that the control modules are not activating suppression systems or controlling
critical facility operations such as computer power. Physically disconnect the wiring to all
CAUTION
agent-release and pre-action-sprinkler circuits and bypass all affected power-off circuits
before activating any control modules if the control modules are activating suppression
systems or are shutting off power. Restore the system to normal operating condition at
the conclusion of all control-module activations and any other functional tests.
8
RRM Group. Activate or De-Activate Remote Release Modules.
Purpose: To manually activate or de-activate one or more remote release modules during system
testing to confirm the proper operation.
Note: All remote release modules must be manually de-activated via a menu operation or a system
reset before the system can be returned to normal operating condition.
There is no indication at the control unit that an output is activated. Be sure to de-activate
the output after proper operation has been confirmed.
Ensure that the remote release modules are not activating suppression systems.
Physically disconnect the wiring to all agent-release and pre-action-sprinkler circuits if
CAUTION
the control modules are activating suppression systems. Restore the system to normal
operating condition at the conclusion of all RRM activations and any other functional
tests.
February 2011
3-44
P/N 06-237041-001