Troubleshooting
SLC Events
Error Message
L#: Addr
TYPE ERROR On
Type
SWITCH INPUT ACTIVE On The contacts of AI device at address
L#: Addr
L#: Addr
FAILED TO CARRY OUT
COMMAND On
L#: Addr
DETECTOR TBL On
AnaLASER Interface Module
February 2011
Table 6-2. SLC Events (Continued)
For the following SLC-related events, L# is the SLC loop number and Addr is the
device address.
Probable Cause
The device at address L#: Addr is
Device
reporting a device type that is different
from the type of device that is
configured for that address
L#: Addr are still connected. This fault
reports when AI is configured for switch
type inputs – Drill, Silence,
Acknowledge, etc. are left active.
An SLC output device at address
L#: Addr failed to process the activation
command.
A problem in a high-sensitivity smoke
detector (HSSD) being monitored by an
AIM/APIC
Corrective Action
• Ensure that the device installed at
• Use Handheld Programmer to test the
• Intermittent type errors could be a
• Disconnect the switch connected to
• Check device to be sure the switch is
• Check device connections to SLC
• Ensure that device has not been
• Check SLC wiring for excessive
• Perform a test to activate the device.
• Replace the device if above
• Check the AIM/APIC-to-HSSD
• Use LaserNET or AIR-Intelligence
• Refer to AnaLASER II Installation,
6-14
address L#: Addr matches the device
type configured for that address.
Install corrected device or correct
configuration file and re-upload
application.
device if the device type matches the
entry in the configuration file. Replace
the device if it fails the test or if the
error message returns when the
device is re-installed.
symptom of SLC wiring problems.
Check SLC wiring if random errors
are reported. Refer to Section 2-8.5.
Ensure that wiring-resistance and -
capacitance limitations have not been
exceeded.
the AI device
properly wired
wiring
removed
capacitance and/or resistance if the
device LED is blinking. Refer to
Section 2-8.5. Rewire SLC using
recommended wire in Appendix B.
procedures are unsuccessful.
connections
Remote Configuration Software to
troubleshoot the HSSD.
Operation, and Maintenance Manual,
P/N 89.200 or appropriate AIR-
Intelligence detector manual,
P/N 33-308100-001/-002/-003.
P/N 06-237041-001