UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
Table 2-10 Ports on the monitoring interface card
Port
DO_1
DO_2
DO_3
DO_4
DB26
Battery
temperature
sensor port
Southbound
communicati
ons port 1
Southbound
communicati
ons port 2
Network
port
Northbound
communicati
ons port
Issue 09 (2023-07-10)
Silk
Screen
NO
COM
NO
COM
NO
COM
NO
COM
MDU
B_TEMP
COM1
COM2
FE
RS485
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
● DO_1, DO_2, DO_3, and DO_4 indicate alarm
outputs. The default values are Critical alarm,
Minor alarm, Bypass mode, and Battery mode,
respectively.
● On the LCD, choose System Info > Settings >
Dry Contact Settings. Set MUS05A DO_1,
MUS05A DO_2, MUS05A DO_3, and MUS05A
DO_4 to Disable, Critical alarm, Major alarm,
Minor alarm, Bypass mode, Battery mode,
Low batt. volt., Batt. SOC below thres.,
Abnormal mains, Sys maint breaker enable,
Sys outp breaker enable, Maint. breaker
closed, No power supplied, Mains supplies
power, ECO mode, Battery test, Batt. volt.
below thres, Rack output overload, Battery
temp. abnormal, Battery EOD, and BCB
disconnected.
● Configure power segment settings based on
backup time.
Provides FE, RS485, I2C, and CAN signals.
Connects to an indoor battery temperature sensor.
● Supported protocol: Modbus-RTU.
● Connects to an ambient temperature and
humidity sensor over two wires.
● Supported protocol: Modbus-RTU.
● Connects to a southbound device.
● Supported protocols:
Versions earlier than XXXX: Modbus-TCP, HTTPS,
and SNMP.
Versions later than XXXX: Modbus-TCP, HTTPS,
BIN, and SNMP.
● Connects to the network port on a PC.
● Network port for connecting to the web service
and for SNMP networking.
● Supported protocol: Modbus-RTU.
● Connects to a northbound network
management device or a third-party network
management device over two wires.
2 Product Overview
49