UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
● Connect cables from bottom up in this sequence: bypass input power cables,
● When connecting cables, tighten bolts from inside out to secure cables.
● Before connecting cables, ensure that all UPS input switches are turned off.
● Connect the input power cables to the UPS before connecting power cables to
Figure 3-34 Grounding
Step 6 Connect the bypass input power cables. (Perform this step only when the mains
input and bypass input use different power sources.)
Issue 09 (2023-07-10)
NO TICE
output power cables, mains input power cables, and battery input power
cables.
Attach warning labels to avoid misoperations on switches.
customer equipment.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
96