UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
Table 3-1
currents listed in the tables are measured at a rated voltage of 380 V.
Table 3-1 Recommended cross-sectional areas for power cables
Item
Mains
Input current (A)
input
Recommende
d cross-
sectional area
2
(mm
)
Bypass
Input current (A)
input
Recommende
d cross-
sectional area
2
(mm
)
Output
Output current (A)
Recommende
d cross-
sectional area
2
(mm
)
Battery
Nominal battery
input
discharge current (A)
Maximum battery
discharge current (A)
Recommende
d cross-
sectional area
2
(mm
)
Issue 09 (2023-07-10)
lists the recommended cross-sectional areas for UPS power cables. The
400 kVA
640
L1
2 x (4 x 185)
L2
L3
N
PE
185
608
L1
2 x (4 x 185)
L2
L3
N
PE
185
608
U
2 x (4 x 185)
V
W
N
PE
185
789
945
+
2 x (3 x 185)
N
-
PE
185
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
Copyright © Huawei Digital Power Technologies Co., Ltd.
500 kVA
800
3 x (4 x 185)
2×150
760
3 x (4 x 185)
2×150
760
3 x (4 x 185)
2×150
987
1182
3 x (3 x 150)
240
3 Installation
600 kVA
960
3 x (4 x 240)
2×185
912
3 x (4 x 240)
2×185
912
3 x (4 x 240)
2×185
1184
1418
3 x (3 x 240)
2×185
67