Configuring the safety sensor
NOTICE
If in the Resolution and Max. AGV speed input fields you select values > 0, the application usu-
ally used for the bank is displayed in the Application field, e.g. Point of operation guarding.
For access guarding, point of operation guarding and danger zone guarding, you must select
Max. AGV speed = 0!
Ä In the RESPONSE TIME dialog box, select the response time of the safety sensor.
Ä In the START-UP BEHAVIOR dialog box, select the start-up behavior and the restart time of the safety
sensor.
NOTICE
Configuration of the start-up behavior is only implemented if the corresponding electrical signal
connections exist; see chapter 8 "Electrical connection".
NOTICE
When the safety sensor is configured, the set restart time should correspond to at least the se-
lected response time.
Ä In the EXTENDED OUTPUT SIGNALS dialog box, activate the definition of output signals.
Ä Click the [Confirm] button.
Ä Configure all other banks of the protective function following the described procedure.
Create protective and warning fields
A field pair consists of one protective field and one warning field.
Ä In the CONFIGURATION menu, right-click the Bank 1 option under Protective function_A
Select Add field pair.
ð The Add field pair dialog box opens.
Ä In the Field pair list, select the number of the field pair and click the [Add] button. When you have
added all field pairs for the bank, click [Close].
ð The added field pairs are shown in the CONFIGURATION menu as an option under Bank 1 under Pro-
tective function_A. The Parameters option is displayed for each field pair.
Ä Add the field pairs for the other banks of Protective function A if one protective function with multiple
configuration banks has been selected.
ð The added field pairs are shown in the CONFIGURATION menu under Bank [x] under Protective func-
tion A.
Configure protective and warning fields
Defining contours and boundaries for protective field and warning field
Leuze electronic GmbH + Co. KG
RSL 440
90