Diagnosis and troubleshooting
Diagnostic
Diagnostic message
ID
E0588
Optics cover is soiled.
I0604
Optics cover is soiled.
P0653
Safety configuration is not compatible: pro-
tective/warning field radius too large.
P0654
Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: field pair not de-
fined.
I0660
Field pair changeover is not performed in
accordance with the specifications config-
ured in the safety sensor: no field pair acti-
vated at system start.
U0661
Safety-related switching outputs (OSSDs)
cannot be switched: short circuit with 0 V,
+24 V DC or between OSSDs.
I0719
Timeout of signals RES1 or RES2 (acknowl-
edgment button, start/restart).
P0747
Safety configuration is not compatible: pro-
tective/warning field radius too small.
I0825
Simulation mode has been activated.
I0826
Simulation mode has been deactivated.
I0859
Configuration was reset.
I1004
Field violation due to glare.
(With switch-off of the OSSDs)
I1005
Dazzled RSL.
(Without switch-off of the OSSDs)
F....
The monitoring functions have detected an
internal error.
Leuze electronic GmbH + Co. KG
Measure
Clean the optics cover.
Clean the optics cover as soon as possible.
Sensor is still in safety mode.
Swap out the safety sensor or change the
configuration. The type of safety sensor must
be the same as the type stored in the connec-
tion unit or in the Sensor Studio software.
Check the wiring of function inputs F1 to F10
and that the parameter settings in the configu-
ration are correct.
Check the wiring of function inputs F1 to F10
and that the parameter settings in the configu-
ration are correct.
Check the wiring of the OSSDs.
Check the wiring of inputs RES1 and RES2.
The time specifications for start/restart must
be observed.
Change the dimensions and contour of the
protective field in the configuration. The mini-
mum range of the protective field must be ob-
served.
The safety-related switching outputs (OSSDs)
have been switched off.
Safety sensor is again in safety mode.
CAUTION!
Be aware of potential hazards which can oc-
cur when the machine is started up!
+24 V detected at RES input after switch-on.
The communication parameters were reset to
default values.
Mount the safety sensor so that the light
source does not hit the outlet disc directly.
Mount the safety sensor so that the light
source does not hit the outlet disc directly.
Create the service file (see chapter 4.5.5 "DI-
AGNOSIS") and contact the Leuze customer
service (see chapter 14 "Service and sup-
port").
RSL 440
106