Emerson Rosemount 702 Quick Installation Manual page 12

Wireless discrete transmitter
Hide thumbs Also See for Rosemount 702:
Table of Contents

Advertisement

Rosemount 702
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECExBAS07.0082X
Ex ia IIC T4 (-60 °C <= T
IP66 / IP67
For use with Rosemount SmartPower options P/N 753-9220-XXXX only
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than 1 gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
TABLE 3. Sensor Parameters
Sensor
U
= 6.6 V
o
I
= 26 mA
o
P
= 42.6 mW
o
C
= 10.9 uH
o
L
= 500 mH
o
Japanese Certifications
I4 TIIS Intrinsic Safety
Ex iia IIC T4
Certificate
TC18457
TC18640
China (NEPSI) Certifications
I3 China Intrinsic Safety
Certificate No. (Manufactured in Chanhassen or Singapore): GYJ081015
Ex ia IIC T4/T5
Special Condition for Safe Use
1. The temperature class depends on ambient temperature range as follows:
Temperature Class Ambient Temperature Range
T4
T5
2. Safety Parameters:
Sensor
U
= 6.6 V
o
I
= 26.2 mA
o
P
= 42.6 mW
o
C
= 10.9 uF
o
L
= 25 uH
o
12
<= 70 °C), Ex ia IIC T5 (-60 °C <= T
amb
Description
Frequency/Protocol Option WA1
Frequency/Protocol Option WA3
(-60 ~ +70) °C
(-60 ~ +40) °C
Quick Installation Guide
00825-0100-4702, Rev BA
August 2009
<= 40 °C)
amb

Advertisement

Table of Contents
loading