4. Requirement

4.1.

Transportation

The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is
recommended to keep the original package for future need.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
4.2.

Placement

This product meets the safety requirements for devices to be operated in restricted access locations according to EN
60950-1 safety standard, which states that the owner should guarantee the following:
• Access to the equipment can only be gained by service persons or by users who have been instructed about the
reasons for the restrictions applied to the location and about any precautions that shall be taken and,
• Access is through the use of a tool or lock and key, or other means of security and is controlled by the authority
responsible for the location.
• UPS is not designed for outdoor application.
• The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
• Recommended operating temperature and humidity values are listed on the Appendix-1 Technical Specifications.
• Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
• The connection and the circuit breakers are at the front of UPS. Leave access at the front of the UPS for maintenance.
(Refer to Figure.4.2-4)
• Air outlets of the UPS are at the front, back and on both sides. Leave access at the front side, back side and from both
lateral sides for ventilation and battery replacement. (Refer to Figure.4.2-1, 4.2-2, 4.2-3 and 4.2-4)
• Recommended environmental humidity condition is between 20-95% (non-condensing).
Environment Requirement
Model (kVA)
Max. dissipation at full load
Storage temperatures
Working temperature
Maximum relative humidity
Maximum altitude without derating
Degree of protection
Colour cabinet
40
(W)
3638
(BTU)
12415
-25/+55 °C (-13/131 °F) (15-25 °C for maximum battery life)
0/40 °C (32/104 °F) (15-25 °C for maximum battery life)
95% max. without condensation
1.000 m (3.300 ft)
IP 20 (other IP as option)
RAL 7016@enclosure RAL 9005@front door metal
Table.1
KEOR T
50
60
4392
4962
14988
16930
7