KEOR T
TWO PARALLEL UNITS 1+1 Redundant Configuration with Single Distribution Input
a1, a2:
Mains Supply MCCB 4p
d:
Distribution MCCB
o1, o2
unit output switch 4p
NOTE:
Q3=
Internal Maintenance Bypass can be used when total load < single unit rating (kVA)
o1,
o2= unit output disconnect switch to enable single unit complete shut down for maintenance
Option
a, o
should be 4poles unless TN-C distribution is used