6.2.

Internal SNMP Communication

Internal SNMP card can be installed into SNMP slot placed at the front of UPS. As soon as SNMP installed,
RS232 port would be disabled.
Internal SNMP has the same features as External SNMP; refer to Section 6.1 for more information.
SNMP
NMP JUMPER (J2 – J3):
If internal SNMP would be used, 2 jumpers should be moved to upper side.
If RS232 or RS485 would be used, 2 jumpers should be moved to lower side.
If the jumpers are at the upper side for internal SNMP configuration, RS232 and
RS485 Serial Communication are disabled.
If the jumpers are at the lower side for RS232 or RS485 configuration, internal
SNMP is disabled.
KEOR T
RS232 - RS485
35