Installation Parameters
Model (kVA)
Phase in/out
Rated output apparent power (kVA)
Rated output active power (kW)
Rated input current (A) at 400V nominal input voltage
Maximum input current (A) at 340V input voltage + full load +
battery charging
Rated bypass current (A) at 400V nominal input voltage
Maximum bypass current (A) at 400V, 125% overload 10 min
Inverter output current @ 400V (A)
Maximum Inverter output current (A) at 400V, 125% overload
10 min
Overload tolerated by the inverter (with mains
power present) (kW)
Recommended Protection Devices – Rectifier/Mains Supply –*
MCB-MCCB (A) (3 or 4 pole according neutral system)
GG fuse (A)
Recommended Protection Devices – General Bypass/Auxiliary Mains Supply –*
MCCB (A) (3 or 4 pole according neutral system)
Maximum I2t supported by the bypass (A2s) (10ms)
Icw max (A)
Protection Devices – Battery Fast Fuse –
HIGH SPEED Dual Indication Fuse-Links Square Body - 690V
(A)
Recommended Protection Devices – Output
C curve circuit breaker (A) (3 or 4 pole according neutral
system)
B curve circuit breaker (A) (3 or 4 pole according neutral
system)
Maximum inverter short circuit current for 50 ms: IK1=IK2=IK3
=IF (A)
Min-Max. Cable Cross-Section for Terminals**
Rectifier (mm²)
General Bypass (mm²)
Battery (mm²)
Output (mm²)
Neutral (mm²)
Protective Earth/Bonding
Leakage Current Protection ***
10
40
40
36
110
139
116
145
111
137
10 min
90
1 min
108
125 D-type
125
20
25300
125 (German
Standard Knife
Blade, Size 000)
≤20
≤40
210
50
50
50
50
50-70
Recommended cross section for ground wire at least half of the
section of cable phases AND shall comply with the standards of
the country (for example NFC 15100 in France).
Minimum 300 mA delayed (Type-B). When used, the residual
current earth leakage protection system must be common for
the two AC inputs (common & auxiliary mains) and installed
upstream.
Table.2
50
3Ph+N+PE / 3Ph+N+PB
50
45
137
173
145
181
139
174
112.5
135
160
160
25
10000
160 (DIN 43 620)
(DIN 43 653)
≤20
≤50
320
50-70
50-70
50-70
50-70
70
60
60
54
165
207
174
217
167
209
150
162
200
175
40
320000
160
≤32
≤63
360
50-95
50-95
50-95
50-95
70-95