Appendix-2: Modbus List

While reading data through MODBUS, the following addresses can be used. "03 - Read Holding Registers"
must be selected to read the MODBUS data.
We can send commands by using MODBUS. To do that function 06 – Write Single Register must be used.
The data is defined as unsigned words (2 bytes).
Address
Coefficient
Data Definition
100
1
L1 Input Voltage
101
1
L2 Input Voltage
102
1
L3 Input Voltage
103
1
L1 Input Current
104
1
L2 Input Current
105
1
L3 Input Current
106
0,1
Input Frequency
107
1
L1 Output Voltage
108
1
L2 Output Voltage
109
1
L3 Output Voltage
110
1
L1 Output Current
111
1
L2 Output Current
112
1
L3 Output Current
113
0,1
Output Frequency
114
1
L1 Output Load Percentage
115
1
L2 Output Load Percentage
116
1
L3 Output Load Percentage
117
1
L1 Bypass Voltage
118
1
L2 Bypass Voltage
119
1
L3 Bypass Voltage
120
1
Positive Battery String Voltage
121
1
Negative Battery String Voltage
122
1
Positive Battery String Current
123
1
Negative Battery String Current
124
1
Battery / Ambient Temperature
125
1
Positive DC Bus String Voltage
126
1
Negative DC Bus String Voltage
127
1
UPS Conditions and Alarms (***)
201
1
If "1" is sent then beeper will be on. If "0" is sent then beeper will be off.
202
1
If "1" is sent then a battery test will start.
KEOR T
Read (R) / Write (W)
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W