Also we can use addresses 127 to get the UPS status. A decimal value will be received from address 127.
If that value is converted to binary number, the UPS status can be read.
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit 10
bit 11
bit 12
bit 13
bit 14
Example:
111000000000001 will be obtained. Then the following status can be read from that number:
Online Mode
ESD interface is activated
DC Bus voltage is out of limits
General Alarm
42
UPS operates on Online Mode
UPS operates on Bypass Mode
UPS operates on Battery Mode
Output voltage is out of limits
Output overload
Inverter temperature is high
Rectifier temperature is high
Ambient temperature is high
Bypass is not synchronized
Maintenance Bypass Breaker is "ON"
UPS operates on Green Mode
Battery Failure
ESD interface is activated
DC Bus voltage is out of limits
General Alarm
Let's receive 28673 (DEC) from address 127. If that value is converted to binary number,