Power Connections of Single Systems

Make sure that all circuit breakers are "OFF" before starting with the installation.
The power screw terminals are located on the lower front side of the UPS.
Firstly, open the UPS door, screw out of the metal cover, afterwards open plastic cover of terminals.
After the covers are removed, the cables shall be passed through the hole under the terminals.
After all connections done, replace the covers in order.
Figure.5.3.1-1
Figure.5.3.1-2
40-50kVA KEOR T
60kVA KEOR T
KEOR T
15