Appendix-3: Description of UPS and Block Diagram

Name
Definition
Q1
Common Mains Supply Circuit Breaker
Q2
Output Circuit Breaker
Q3
Maintenance Bypass Circuit Breaker
Q4
Auxiliary Mains Supply Circuit Breaker
F5
Battery Fast Fuse
Q6
Inrush Circuit Breaker
F1
Rectifier Fast Fuse
F2
Inverter Fast Fuse
KREC
Rectifier Contactor
KINV
Inverter Contactor
KBYP*
Backfeed Contactor (shunt trip)
X1
Common Mains Supply Terminals
X2
Output Terminals
X4
Auxiliary Mains Supply Terminals
In case any inverter fault occurs; Bypass thyristors transfer the supply of the load electronically from inverter to Auxiliary
BYPASS THYRISTOR
Mains Supply without any interruption.
RECTIFIER
The rectifier generates a very constant DC voltage level by drawing current from the input with a power factor close to 1.
INVERTER
The inverter generates a very constant AC voltage level at the output by using DC voltage source at the rectifier's output.
BATTERY
Supplies the necessary energy when the mains voltage is not available.