Conditions Of Installation; Flue And Chimney Suitability - Flavel Linear HE Installation, Maintenance & User Instructions

Inset live fuel effect gas fire
Table of Contents

Advertisement

1.1

CONDITIONS OF INSTALLATION

It is the law that all gas appliances are installed only by a Registered Installer, in
accordance with these installation instructions and the Gas Safety (Installation and
Use) Regulations 1998 as amended. Failure to install appliances correctly could
lead to prosecution. It is in your own interest and that of safety to comply with the
law.
The installation must also be in accordance with all relevant parts of the Local and
National Building Regulations where appropriate, the Building Regulations
(Scotland Consolidation) issued by the Scottish Development Department, and all
applicable requirements of the following British Standard Code of Practice.
1. BS 5871 Part 2 Installation of Inset Fuel Effect Gas Fires
2. BS 6891 Installation of Gas Pipework
3. BS 5440 Parts 1 & 2 Installation of Flues and Ventilation
4. BS 1251 Open fire place components
5. BS 715 / BS EN 1856-2 Metal flue pipes for gas appliances
6. BS 6461 Part 1 Installation of masonary chimneys and flues
7. IS 813 : 1996 Domestic Gas Installation (Republic of Ireland)
No purpose made additional ventilation is normally required for this
appliance, when installed in G.B. When Installing in I.E. please consult
document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the
National Standards Authority of Ireland. If installing in Northern Ireland,
please consult local building regulations. In Scotland, please consult the
current edition of the Building standards regulations, issued by the Scottish
Executive. Any purpose made ventilation must be checked periodically to
ensure that it is free from obstruction.
1.2

FLUE AND CHIMNEY SUITABILITY

This appliance is designed for use with conventional brick built or lined chimneys
and fabricated flues and metal flue boxes conforming to BS 715 / BS EN 1856-2.
All flues must conform to the following minimum dimensions.
Minimum diameter of circular flues
Minimum effective height of all flue types
When fitting to conventional chimneys or 175mm flues it may be desirable to
fit the flue restrictor baffle (supplied) to reduce the flue flow and increase the
efficiency of the fire. Safe clearance of products must always be checked by
carrying out a smoke match test as described.
INSTALLATION REQUIREMENTS
125 mm (Without flue
restrictor fitted)
4 metres
4