Daikin ERHQ011BA Installer's Reference Manual

Low temperature split
Hide thumbs Also See for ERHQ011BA:
Table of Contents

Advertisement

Quick Links

INSTALLER
REFERENCE GUIDE
Daikin Altherma - Low Temperature Split
+
ERHQ011BA
ERHQ014BA
ERHQ016BA
ERLQ011CA
ERLQ014CA
ERLQ016CA
EHBH16CA
EHBX16CA

Advertisement

Table of Contents
loading

Summary of Contents for Daikin ERHQ011BA

  • Page 1 INSTALLER REFERENCE GUIDE Daikin Altherma - Low Temperature Split ERHQ011BA ERHQ014BA ERHQ016BA ERLQ011CA ERLQ014CA ERLQ016CA EHBH16CA EHBX16CA...
  • Page 2: Table Of Contents

    9.6.4 To interrupt an underfloor heating screed dryout ....61 ................... 22 6.3.4 Overview of electrical connections for external and internal 10 Hand-over to the user actuators................22 Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 3: About The Documentation

    12.3.8 Symptom: Decoration panels are pushed away due to a swollen tank................65 Latest revisions of the supplied documentation may be available on 12.4 Solving problems based on error codes.........65 the regional Daikin website or via your dealer. 12.4.1 Error codes: Overview ............66 13 Glossary General safety precautions 14 Technical data 14.1 Dimensions and service space ............69...
  • Page 4: For The Installer

    Name and address of fire department, police and hospital Name, address and day and night telephone numbers for obtaining service In Europe, EN378 provides the necessary guidance for this logbook. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 5: Electrical

    Do NOT throw away the upper cardboard cover. On the inside of the cardboard cover, the installation pattern is Make sure all covers are closed before starting up the printed. unit. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 6: To Remove The Accessories From The Indoor Unit

    You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1). For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 7: Possible Combinations Of Indoor Unit And Outdoor Unit

    4.2.2 Possible combinations of indoor unit and outdoor unit Indoor unit Outdoor unit EHBH16CA3V EHBX16CA3V EHBH16CA9W EHBX16CA9W ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 ERLQ011CAV3 ERLQ014CAV3 ERLQ016CAV3 ERHQ011BAW1 ERHQ014BAW1 ERHQ016BAW1 ERLQ011CAW1 ERLQ014CAW1 ERLQ016CAW1 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 8: Possible Combinations Of Indoor Unit And Domestic Hot Water Tank

    Setting up the space heating/cooling system unit and used for control close to the indoor unit + user The Daikin heat pump system supplies leaving water to heat emitters interface (optional equipment EKRUCAL) installed in the in one or more rooms.
  • Page 9 Cooling. The heat pump convector offers, besides heating capacity, also excellent cooling capacity. Benefits Efficiency. Optimal energy efficiency because of the interlink Wireless. The Daikin external room thermostat is available in a function. wireless version. Stylish. Efficiency. Although the external room thermostat only sends...
  • Page 10: Multiple Rooms - One Lwt Zone

    NOT need a mixing valve station (cost effective). Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 11: Room Thermostats

    (X2M/1 and X2M/4). The indoor unit will only supply leaving water temperature when there is an actual demand. NOTICE To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector.
  • Page 12: Multiple Rooms - Two Lwt Zones

    5 Application guidelines Setup NOTICE To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector. Configuration Setting Value Unit temperature control: 0 (LWT control): Unit operation is decided based on the leaving #: [A.2.1.7]...
  • Page 13: Setting Up An Auxiliary Heat Source For Space Heating

    (status of the changeover to external heat source). Daikin is NOT responsible for incorrect or unsafe When the permission is given to the auxiliary boiler, the space situations in the auxiliary boiler system.
  • Page 14: Setting Up The Domestic Hot Water Tank

    Contact the manufacturer of the h Collector (field supply) i DHW tank auxiliary boiler for more information. j Heat exchanger coil FHL1...3 Under floor heating Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 15: Selecting The Volume And Desired Temperature For The Dhw Tank

    5.4.5 Combination: Standalone DHW tank + Solar If energy prices are the same during the day and the night, panels Daikin recommends to heat up the DHW tank during the By connecting the DHW tank to solar panels, the DHW tank can be day.
  • Page 16: Dhw Pump For Instant Hot Water

    ALL power input of the system is covered by the electrical power meters. Configuration The indoor unit can control DHW pump operation. For more information, see the configuration chapter. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 17: Normal Kwh Rate Power Supply

    You only need to set the number of pulses of each power meter. See preferential kWh rate power supply for an example with two power meters. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 18: Permanent Power Limitation

    Power limitation is also useful in combination with an energy management system. Then set the heater priority The power or current of the entire Daikin system is limited If… has priority via the user interface to… dynamically by digital inputs (maximum four steps). Each power Domestic hot water production Booster heater.
  • Page 19: Setting Up An External Temperature Sensor

    That is NOT affected by outside air or air draught because of, for example, door opening/closing If this is NOT possible, Daikin recommends to connect a remote indoor sensor (option KRCS01-1). Setup: For installation instructions, see the installation manual of the remote outdoor sensor.
  • Page 20: Preparing Water Piping

    If air, moisture or dust gets into the water circuit, problems may occur. To prevent this: Only use clean pipes Hold the pipe end downwards when removing burrs. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 21: Formula To Calculate The Expansion Vessel Pre-Pressure

    (a) This is the height difference (m) between the highest point of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0 m. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 22: Changing The Pre-Pressure Of The Expansion Vessel

    At that moment, the outdoor unit compressor will not operate. Whether the power supply is interrupted or not, the wiring to the unit is different. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 23: Overview Of Electrical Connections Except External Actuators

    4 Preferential kWh rate power supply (voltage free contact) 5 Normal kWh rate power supply (to power the indoor unit PCB in the event of power supply interruption of the preferential kWh rate power supply) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 24: Overview Of Electrical Connections For External And Internal Actuators

    Power supply for bottom plate heater Room thermostat 3 or 4 100 mA Outdoor ambient temperature sensor Indoor ambient temperature sensor Heat pump convector 100 mA Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 25: To Open The Switch Box Cover Of The Indoor Unit

    If this is NOT working correctly, overpressure will deform the tank and water leakage may occur. To confirm good operation, regular maintenance is required. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 26: To Fill The Water Circuit

    Connecting the electrical wiring DANGER: RISK OF ELECTROCUTION INFORMATION More information about the legend and the location of the wiring diagram of the unit can be found in Wiring diagram. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 27: To Connect The Main Power Supply

    The backup heater capacity can vary, depending on the indoor unit model. Make sure that the power supply is in accordance with the backup heater capacity, as listed in the table below. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 28 K2M/1 ∞ ∞ ∞ ∞ ∞ L1 L1 L2 L2 L3 L3 L1 L2 L3 (*9W) (a) For configuration of the backup heater, see Quick wizard: Standard. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 29: To Connect The User Interface

    The PCB is mounted in the faceplate of the user interface. Be careful NOT to damage it. From the left Fix the wallplate of the user interface to the frontplate of the unit. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 30: To Connect The Shut-Off Valve

    Installation of EKRP1HB is required. Fix the cable with cable ties to the cable tie mountings. Fix the cable with cable ties to the cable tie mountings. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 31: To Connect The Space Cooling/Heating On/Off Output

    When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. a Installation of EKRP1AHTA is required. Fix the cable with cable ties to the cable tie mountings. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 32: Configuration

    For proper operation of the system, the local data on the two user interfaces must be the same. If this is not the case, both user interfaces will display: Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 33: To Copy The Language Set From The First To The Second User Interface

    3 (3P,(1/1+2)): 6 kW 3~ 230 V (*9W) (3PN,(1/2)): 6 kW 3N~ 400 V (*9W) Set the current date and time. 5 (3PN,(1/1+2)): 9 kW 3N~ 400 V (*9W) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 34 RT control is selected act as room thermostat. In room(default): the other user interface is automatically set to At unit and if RT control is selected to act as room thermostat. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 35: Quick Wizard: Options

    EHBH/X: an optional domestic hot water tank is available, EHVH/X: a domestic hot water tank is standard incorporated into the indoor unit. Following settings must be made accordingly. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 36 Modification of these settings is only needed when the optional digital I/O PCB is installed. The digital I/O PCB has multiple functionality which need to be configured. See "5 Application guidelines" on page 6. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 37: Quick Wizard: Capacities (Energy Metering)

    Bottom plate heater: Only applies to an optional bottom plate heater (EKBPHTH16A). The capacity of the optional bottom plate heater at nominal voltage. Default: 0 W. 0~200 W (in steps of 10 W) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 38 Note: This value should be lower than [1-02] as for high outdoor than [1-08] as for high outdoor temperatures less warm water is temperatures colder water required. required. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 39 Remark: This value can only 25°C). leaving water Note: This value should be lower temperature control. than [0-01] as for high outdoor temperatures less warm water is required. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 40 Range: 3~10°C (in steps of 1°C; default value: 5°C). [A.3.1.3.2] [9-0A] Cooling: required temperature difference between entering and leaving water. Range: 3~10°C (in steps of 1°C; default value: 5°C). Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 41: Domestic Hot Water Control

    [A.4.4.2]: Operation day. [A.4.3.2.1] 1 person The increment of the desired tank temperature for 2 persons compared to 1 person. 0~20°C (default: 4°C) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 42: Advanced Configuration/Optimization

    18~20°C to prevent condensation on the Code Description floor. [9-04] 1~4°C (default: 1°C) Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 43 Only applicable in case of room thermostat control. The hysteresis desired leaving water temperature can be increased or lowered by band around the desired room temperature is settable. Daikin 3°C. Increasing the modulation results in better performance (less advises NOT to change the room temperature hysteresis as it is set On/OFF, faster heat up), but note that depending on the heat emitter, for an optimal use of the system.
  • Page 44 OFF to avoid overheating. Code Description [A.3.3.1] [4-02] EHBH/X04+08 and EHVH/X04+08: 14~25°C (default: 25°C) EHBH/X16 EHVH/X16: 14~35°C (default: 35°C) The same setting is also used in automatic heating/cooling changeover. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 45: Domestic Hot Water Control: Advanced

    Storage eco: The storage economic temperature denotes the lower desired tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day). Code Description [7.4.3.2] [6-0B] 30~80°C (default: 45°C) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 46 Hysteresis. Temperature difference between booster heater ON and booster heater OFF temperature. The minimum hysteresis temperature is 2°C. [6-00] The temperature difference determining the heat pump ON temperature. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 47 CAUTION Be sure that the disinfection function start time [A.4.4.3] with defined duration [A.4.4.5] is NOT interrupted by possible domestic hot water demand. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 48: Heat Source Settings

    Make sure to observe all rules mentioned in application 0: Disabled guideline 5 when bivalent operation function is enabled. 1: Enabled Daikin shall not be held liable for any damage resulting 2: Limited, only enabled during from failure to observe this rule. domestic hot water operation of for system with integrated domestic hot water tank.
  • Page 49: System Settings

    (by heat pump), which operation mode has priority? 0: The operation mode with the highest request has priority. 1: Always space heating/cooling has priority. YC Y1 Y3 Y4 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 50 INFORMATION function reapplies the remote controller settings at the time of the Only applicable for ERLQ004~008CAV3. power failure. Therefore, Daikin recommends to always enable the function. Defines whether the outdoor unit power supply can be interrupted If the preferential kWh rate power supply is of the type that power (internally by indoor unit control) during stand-still conditions (no supply is interrupted, always enable the auto restart function.
  • Page 51 0~50 A, step 1 A (default: 50 A) [A.6.3.5.2] [5-06] Limit DI2 0~50 A, step 1 A (default: 50 A) [A.6.3.5.3] [5-07] Limit DI3 0~50 A, step 1 A (default: 50 A) EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 52 This functionality is only valid in specific conditions where it is preferable to keep the pump active when <4°C (pump will be activated for 10 minutes and disactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality. Installer reference guide...
  • Page 53: Menu Structure: Overview

    8 Configuration Menu structure: Overview EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 54: Menu Structure: Overview Installer Settings

    8 Configuration Menu structure: Overview installer settings Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 55: Commissioning

    The stop valves (gas and liquid) on the outdoor unit are function. fully open. Result: Air purging is started and following screen will be shown. The air purge valve is open (at least 2 turns). EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 56: To Perform An Automatic Air Purge

    > Set dryout schedule. turned OFF via the user interface. Go to [A.7.4]: > Installer settings > Commissioning > Actuator test run. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 57: To Start An Underfloor Heating Screed Dryout

    Select OK and press Water pressure Result: The underfloor heating screed dryout program is stopped. Check whether the water pressure is above 1 bar. If it is lower, add water. EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 58: Troubleshooting

    OFF. WARNING If the internal wiring is damaged, it has to be replaced by the manufacturer, its service agent or similarly qualified persons. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 59: Solving Problems Based On Symptoms

    The expansion vessel is not broken. The pre-pressure setting of the expansion vessel is correct (see To set the pre- pressure of the expansion vessel). EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 60: Symptom: The Pressure Relief Valve Opens

    Error code code Description button. Zero cross detection problem. Power reset required. Please contact your dealer. Backup heater overheated. Power reset required. Please contact your dealer. Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 61: Glossary

    Please contact your dealer. accompanying documentation. Room temperature sensor Field supply: problem. Equipment not made by Daikin that can be combined with the Please contact your dealer. product according to the instructions in the accompanying External temperature documentation. sensor problem.
  • Page 62: Technical Data

    SHUT OFF VALVE WITH DRAIN/FILL VALVE (1-1/4˝ F BSP) (INCLUDED ACCESSORY) WATER FILTER POWER SUPPLY/COMMUNICATION WIRE ENTRANCE SERVICE DOOR SWITCHBOX TERMINALS 3D078464 SWITCHBOX TERMINALS FOR DOMESTIC HOT WATER TANK (OPTION) Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 63: Components

    Backup heater Provides additional heating case cold outdoor temperatures. Also serves as backup in case of malfunctioning of the outdoor unit. Air valve EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 64: Components: Switch Box (Indoor Unit)

    Socket X13A, receives the K3M connector. (Only for installations with domestic hot water tank) Main PCB A1P Socket X9A, receives the thermistor connector. (Only for installations with domestic hot water tank) PCB fuse FU1 Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 65: Components: Controller (Indoor Unit)

    Filter m Heat exchanger R1T Outlet water heat exchanger thermistor R2T Outlet water backup heater thermistor R3T Refrigerant liquid side thermistor R4T Inlet water thermistor Heating Cooling EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 66: Piping Diagram

    Refrigerant liquid side thermistor Outlet water backup heater thermistor Outlet water heat exchanger thermisto FLARE CONN. QUICK COUPLING THERMISTOR DESCRIPTION FLANGE CONN. SPINNED PIPE BRAZED CONN. PINCHED PIPE 3D078212 Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 67: Wiring Diagram

    * : optional On/OFF thermostat (wired) (*) : standard for *HV*, optional for *HB* On/OFF thermostat (wireless) # : field supply Ext. thermistor Heat pump convector 4D077028 page 1 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 68 Only for demand PCB option only for EKBPHT* only if no EKBPHT* Options: bottom plate heater OR On/OFF output Only for digital I/O PCB option 4D077028 page 3 Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 69 Add LWT zone DHW pump NC valve 3 wire type (SPST) only for domestic Shut-off valve hot water option only for *04* and *08* 4D077028 page 4 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 70: Power Supply

    In case user interface is relocated 2x0.75 X5M: 1-2 A2P: P1-P2 user interface communication OPTIONAL PART Only for *KRCAL* 2 core 2x0.75 communication A2P: P1-P2 user interface 4D078494 Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 71 Backup heater element (2 kW) Thermal protector backup heater Backup heater element (3 kW) Thermal protector booster heater Booster heater (3 kW) Outlet water heat exchanger thermistor Overcurrent fuse backup heater EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 72 Remote user interface Remote user interface Ext. indoor thermistor Extended indoor thermistor Ext outdoor thermistor Extended outdoor thermistor Digital I/O PCB Digital I/O PCB Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 73: Technical Specifications

    (11) BUH 3V/9W can only operate at flow > 12/15 l/min (12) Refer to operation range for differences between RHQ* and RLQ* units (13) DB/WB 7°C/6°C - LWC 45°C ( DT=5°C) 3D078754_B page 1 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 74 (**) : European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤ 75A per phase. 3D078754_B page 2 (***) : System impedance Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 75: Operation Range

    In case such conditions ara expected, the *RLQ must be installed instead. These models contain countermeasures (insulation, heater sheet, ...) to prevent freeze up. 3TW60813-1A EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 76 –15 –20 –20 domestic hot water domestic hot water –25 –25 tank temperature (°C) tank temperature (°C) 40 45 55 60 40 45 INDOOR UNITS: CA-SERIES 3TW60813-2B Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 77 Dry bulb temperature [°C] 1. Refer to psychometric chart for more information. 2. If condensation is expected, installation of EKHBDPCA2 - drainpan kit must be considered. 4D078990 EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 78: Esp Curve

    1) Selecting a flow outside the area of operation can cause damage or malfunctioning of the unit. See also minimum and maximum allowed waterflow range in the technical specifications. 2) Water quality must be according to EN directive EC 98/83 EC 4D078466_B Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 79: Performance

    14 Technical data 14.9 Performance EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 80 14 Technical data Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 81 14 Technical data EHBH/X16 Installer reference guide Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 82: Combination Table

    14 Technical data 14.10 Combination table Installer reference guide EHBH/X16 Daikin Altherma - Low Temperature Split 4P313776-1 – 2012.05...
  • Page 84 4P313776-1 2012.05...

This manual is also suitable for:

Erhq016baErlq011caErlq014caErlq016caErhq014ba

Table of Contents